Device Functionality
2.1 Front Fascia
Trip Ready LED
The steady illumination of Trip Ready LED indicates that required CT current 0.20 ⋅ I
current) in 1-phase or 0.10 ⋅ I
the relay and the relay is having sufficient energy to trip through the impulse output.
Low Battery LED
The low battery LED indicates when the battery voltage falls below the sufficient operating voltage.
User-Programmable LEDs
The 7SR45 Argus Relay consist of 4 user-programmable LEDs which can be configured to protection and
miscellaneous functions. The LEDs (L4 to L7) are programmed to be illuminated as RED. The 4 user-program-
mable LEDs are mapped to Phase IL1/A, IL2/B, IL3/C, IE/E by default.
User-Programmable LED Configuration
The 4 user-programmable LEDs are assigned to any functions using OUTPUT CONFIG > OUTPUT MATRIX
menu.
The 4 user-programmable LEDs are mapped to Phase IL1/A, IL2/B, IL3/C, IE/E by default. This default configura-
tion shall be printed on one side of the paper label provided with the decal. If you decide to change the config-
uration for the programmable LEDs, then you must write the name of the function (to which the program-
mable LED is mapped) on the rear side of the paper label provided with the decal.
If the LEDs are mapped to any protection or phase function, then they will be turned ON when the function
trips. For example if an LED is mapped to the 51-1 function, then the LED will be turned ON when the relay
trips due to 51-1 fault.
If the LEDs are mapped to a miscellaneous function, then the LEDs turn ON as and when the event occurs. For
example if the LED is mapped to BI 1 operated, then the LED is turned ON when BI 1 input is present.
Table 2-2
Parameters
50-1
50-2
51-1
50N-1
50N-2
51N-1
50G-1
50G-2
51G-1
50LC
49 Trip
49 Alarm
81HBL2
Active Grp 1
Active Grp 2
General Pickup
IL1 / A
IL2 / B
IL3 / C
5
LEDs cannot be mapped to General Pickup, Prot'n Healthy, Low Battery and IRF. A X shall appear in the HMI for these functions. In
Reydisp Evolution, LED configuration for these functions is disabled.
22
(minimum phase current) in 3-phase or auxiliary power supply is applied to
rated
Binary Output ‑ LED Default Value
Description
50-1 element operate
50-2 element operate
51-1 element operate
50N-1 element operate
50N-2 element operate
51N-1 element operate
50G-1 element operate
50G-2 element operate
51G-1 element operate
50LC/SOTF element operate
49 trip element operate
49 capacity alarm element operate
Inrush element operate
Active Group 1
Active Group 2
5
Pickup detected
Phase A tripped
Phase B tripped
Phase C tripped
(minimum phase
rated
LED Default Value
X
L4
L5
L6
Reyrolle, 7SR45, Device Manual
C53000-G7040-C101-2, Edition 09.2020