Download Print this page

Siemens SB Series Information And Instruction Manual page 65

Encased systems breakers 4000 ampere frame rating
Hide thumbs Also See for SB Series:

Advertisement

External A ccessories
U niversal Test Kit (TS-3 1 )
Enter one of the following letters:
"A"-Phase A or Left Pole
" B "-Phase B or Center Pole
"C"-Phase C or Right Pole
H.
The TS-3 1 will report the type of test you selected and
g ive you a chance to abort the test. For example, if
was pressed above. The TS-3 1 wi l l display:
I nstantaneous Test
Press ENTER to Continue or A to Abort.
If you pressed the letter "A" to abort, you will be asked
to enter agai n .
1
Change:
- Test 2 - Catalog
I .
Press Enter again to start the test. Press any other key
to STOP the test. Once a test has been started , the
TS-31 will respond with :
Trip test. Press Any Key to Abort.
Time Remai n i n g : xx.xxx Sec.
Be careful at this time. Any key press wi l l abort the test.
J.
The test may take anywhere from a fraction of a sec­
ond to minutes to complete, depending on which proce­
d u re was run. If the test passes, the display wil l show
the following, depending on whether the breaker tripped
or not.
Test Passed . xxx.xx seconds
Press any key to continue.
If the breaker tri pped during the test, RESET the circuit
breaker before cont i n u i n g .
K. T h e TS-31 will prompt for t h e next instructions. The
d isplay wi l l show:
Change: 1 - Test 2 - Catalog
Enter one of the fol lowin g n umbers:
" 1 "
- select a new test
"2" - enter a new catalog n umber
"3" - enter a new switch setting
I f you enter " 1 " you wil l be sent to step F. Choosing a "2"
wi l l send the program back to step E. Entering "3" which
sends you back to step E, wi l l be slightly different the
second time throu g h . On the second line after the
prompt for the sett i n g , a number or text i n brackets wil l
appear. This w i l l ind icate the last setting you entered . I f
you DON'T wish t o change a setting , j ust press ENTER.
I f you DO wish to change a sett i n g , type i n the new
setting and press ENTER.
L.
If you pressed "C" when aske d .
You will first be prompted b y :
Cu rrent Transformer Test
Press ENTER to Continue or A to abort.
M . There are additional ERROR messages which may
" I "
3 - Settings:
Note:
3 - Settings
Note:
Note:
Note:
and then for the phase to test. A message will then
appear stating the test results. For example:
CT Resistance Test. Phase X PASSED.
Press any key to conti nue.
appear on the d is play d u r i n g this operation which
were not covered previously
Test Not Running - Check Test Cable.
Press enter to continue.
The test set has sensed that cu rrent is not flowing
properly i n the breaker under test and that there is either
an open or short c i rcuit between the TS-31 and the
breaker trip u n it.
Groun d Fault is NOT avai lable on a SJD69300.
Press any key to continue.
You wi l l get this error message if you enter a choice
that is not avai lable, such as entering "G" in step F for
g round fau lt test on a catalog number that does have
g round fau lt.
I nconclusive Test, Check Settings.
Press any key to continue or A to abort.
Th is warn ing will appear if you attempt to run a
short time test with the instantaneous pickup set
equal to or below the short time pickup. It would
also appear if you tried to run a long time test
with short time pickup set to 2. This is only a
warn i n g : the test can sti l l be r u n . However, passing
or fail i ng the test may not be conclusive.
XX is NOT a Val id Sett i n g .
Press a n y key t o continue.
This message wi l l appear if you enter a setting
va l u e t h at d o e s not e x i s t . For exam p l e a
SM D69700ANGT has conti nuous current settings
of 20, 30, 40, 50, 60, 70, 80, 90, 1 00 percent. If you
were to enter any other value than those l isted,
the above message will appear.
Test Exceeds Capabil ity of TS-3 1 .
Press any key to continue.
This message is not l i kely to occur. If it does, it
means that a test req u i res more c urrent to run than
the TS-31 can produce.
Unit Too Hot, Please Wait.
R u n n i n g many successive h i g h-cu rrent long
time tests may over-heat the test set. It will protect
itself from damage by preventing further tests
u nti l it has had a chance to cool down . The d isplay
w i l l i n d i cate when testing can resume.
73