Siemens SB Series Information And Instruction Manual page 33

Encased systems breakers 4000 ampere frame rating
Hide thumbs Also See for SB Series:

Advertisement

Internal A ccessories
Electric Motor Operator
Midbarrier
W1re T1e
Wire T1 e Mount
Mounting of "B" Switch
Switch Assembly \
"B"
Insulator
"B" Switch Assembly
Switch Assembly
" B '
MTR-Connector
Fuse Connector
Reset
Mechanism
---- -- -- Push L1nk
' ' , ,
" "' , w·
(May Be Phillips Head Screws)
RC+ Connector
RC Connector
J 1 -8
Con nectar
J
Connector
1-9
1 0. ) Connect the MTR-Connector and the Fuse Connector to the
Motor and Fuse Holder. Connect the RC+ Connector and
RC-Connector to the Remote Close Solenoid.
1 1 .) Install the "B" Switch assembly on the reset mechanism
assembly. Make sure to install the Insulator between the
Switch and metal bracket Secure the assembly with the two
1/2"
#4-40
screws. Torque screws to 4-6 in-lbs. Check to
be sure the Actuator fits into the slot in the push link and
x
does not bind .
1 2.) Route the two wires attached to the "B" Switch from the right
side of the breaker to the left side of the breaker. The wires
need to be fed under the mechanism plates.
1 3.) Connect the J 1 -8 Connector and the J 1 -9 Connector.