Encased systems breakers 4000 ampere frame rating
Hide thumbs Also See for SB Series:

Advertisement

External A ccessories
Control Termi nal Blocks
Installation Instructions
Hazardous Voltage.
Will cause severe injury or death.
Turn off and lock out all power supplying the
circuit breaker prior to cover(s) removal or
while cover(s) are removed and when installing
any internal or external accessory.
Replace the cover(s) and shield(s) before power
supplying this device is turned on.
Safety I nstructions
A
NOTE: These instructions outline the recommended
installation procedure.
Mounting of Term inal Block Mounts
A
DANGER
Figure 1
Mounting of Terminal Block Mount
Catalog Numbers: SBTBM
1 .)
Accessory installation should be completed before
the breaker is mounted and connected. If breaker is
installed, turn off and lock out all power supplying
the circuit breaker when installing any internal or
external accessories.
2 . )
I nstallation of this device does not require removal of
the breaker cover.
3.)
Remove the four (4) Phill ips head screws on the
breaker cover. Place the Terminal Block Mount over
the screw holes. Reinstall the screws.
4 . )
Secure the assembly b y tightening the Breaker Cover
screws. Tighten screws up to 8 to 32 in .-lb. torque .
� Breaker Cover
Term i nal Block Mount
.._...,
7
Cover Screw
I
\� �
\ � �
63