Encased systems breakers 4000 ampere frame rating
Hide thumbs Also See for SB Series:

Advertisement

External Accessories
Slidi ng Secondary Disconnects and N eutral Sensor
To install the secondary disconnects:
1 .) Engage Secondary Disconnect molded tabs i nto factory
formed slots as ind icated.
2.) Prior to final installation of the secondary d isconnect, it is
recommended that a drop of LocTite #271 be put on the
8-32 x 5/1 6-inch long counter-sunk screws.
The secondary disconnects are referenced as left top
(LT), left bottom (LB), right top (RT), and right bottom
(RB). Left and right are with respect to the user facing
the breaker. The recommended terminal points for acces­
sories added in the field are illustrated below.
66
Hazardous Voltage.
Will cause severe i njury or death.
Do not attempt to install accessories
with voltage present.
"T" Connectors
"T"
connectors are used to connect power buses to the
SB breakers.
"T" connectors with mounting hardware ( 1 connector and appro­
priate hardware shipped with each kit)
"T"
To install the
connectors:
Mount the
"T"
connectors to the terminal pads with the
1 .
mounting bolts. Use torque value supplied with the "T"
connector kit.
DANGER