Unconditioned Spaces; Acoustical Ductwork; Downflow To Horizontal Conversion; Electrical Wiring - Nordyne Q6SP-090 Series Installation Instructions Manual

Single package electric heat pump rooftop unit
Table of Contents

Advertisement

Unconditioned Spaces

All ductwork passing through unconditioned space must be
properly insulated to prevent condensation and minimize
duct losses. Use insulation with an outer vapor barrier.
Refer to local codes for insulation material requirements.

Acoustical Ductwork

Certain installations may require acoustical lining inside
the supply ductwork. Acoustical insulation must be in
accordance with the current revision of the Sheet Metal
and Air Conditioning Contractors National Association
(SMACNA) application standard for duct liners. Duct lining
must be UL classified batts or blankets with a fire hazard
classification of FHC-25/50 or less.
Fiber ductwork may be used in place of internal duct liners
if the fiber ductwork is in accordance with the current
revision of the SMACNA construction standard on fibrous
glass ducts.
Fibrous ductwork and internal acoustical lining must be
NFPA Class 1 air ducts when tested per UL Standard
181 for Class 1 ducts.

Downflow to Horizontal Conversion

The unit is shipped ready for downflow duct connections.
If horizontal ducts are required, the unit must be converted
according to the directions in the conversion kit for both
the supply and return ducts.

ELECTRICAL WIRING

WARNING:
To avoid the risk of electrical shock, personal
injury, or death, disconnect all electrical power
to the unit before performing any maintenance
or service. The unit may have more than one
electrical power supply.
• Electrical connections must be in compliance with all
applicable local codes and ordinances, and with the
current revision of the National Electric Code (ANSI/
NFPA 70).
• For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

√ Verify that the voltage, frequency, and phase of the
supply source match the specifications on the unit rating
plate.
√ Verify that the service provided by the utility is sufficient
to handle the additional load imposed by this equipment.
See
Table
2,
Table 3, (page
18)
or the unit wiring label for proper high and low
voltage wiring.
√ Verify factory wiring is in accordance with the unit wiring
diagram. Inspect for loose connections.
√ For 3 phase units always check the phase balance as
shown on
page 8
17), and
Table 4, (page

Line Voltage

It is recommended that the line voltage to the unit be
supplied from a dedicated branch circuit containing the
correct fuse or circuit breaker for the unit.
IMPORTANT NOTE:
An electrical disconnect must be installed readily
accessible from and located within sight of the unit.
(See unit data label for proper incoming field wiring).
Any other wiring methods must be acceptable to
authority having jurisdiction.
The power supply for the unit must be in accordance with
the unit wiring diagram, and the unit rating plate. Connect
the line-voltage leads to the corresponding terminals on
the terminal block inside the element access compartment.
Refer to
Figure 10 (page 15)
Use only copper wire for the line voltage power supply
to this unit. If using conduit to bring in supply wiring to
the unit, use only UL listed or recognized conduit and
conduit connections.
All Q6SP model units are shipped factory ready for Single
Circuit Electrical Supply connections. See
3, and
Table 4
or the unit rating label for proper high
voltage wiring requirements. For Dual Electrical Supply
connections see unit rating plate or heater kit installation
instructions for proper high voltage wiring requirements.
Use NORDYNE P/N-917468 Pole Dual Circuit Adaptor
for converting to dual supply connections.
CAUTION:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation.Verify proper
operation after servicing.
Units are shipped from the factory wired for 230 or 460 volt
operation. On 208 - 230V units being placed into 208 volt
operation, remove the lead from the transformer terminal
marked 240V and connect it to the terminal marked 208V.
Overcurrent protection must be provided at the branch
circuit distribution panel and sized as shown on the unit
rating label and according to the National Electric Code
and applicable local codes.
• See the unit rating plate for maximum circuit ampacity
and maximum overcurrent protection limits.
• 1-3/8" conduit openings are supplied for high voltage
field wiring entrance. If smaller openings are required
use suitable (field supplied) reducers to meet specific
conduit size requirements.

Grounding

WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground!
for compartment location.
Table
2,
Table
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q6sp-120 series

Table of Contents