Siemens SENTRON 3WL Reference Manual page 57

Air circuit breakers
Hide thumbs Also See for SENTRON 3WL:

Advertisement

Schematics
L1
AC230
N
PE
AC230
„Emergency STOP”
+
-
DC24
„Automatic RESET”
Schematics of the DIGmat S100 and the SENTRON 3WL non-automatic
air circuit breaker
Application examples
Rated operational
Required series
voltage
breaks at rated voltage
Up to 300 V + 10 %
Over 300 V + 10 %
Up to 600 V + 10 %
Over 600 V + 10 %
Up to 1000 V + 10 %
(version for 1000 V
required, order with "-Z"
and order code A05)
The connection to the circuit breakers is not dependent on direc-
tion and polarity; the circuit diagrams can be adapted
accordingly.
If the parallel or series connections are made directly to the
connecting bars, for thermal reasons the continuous load on the
circuit breakers must only be 80 % of the permissible operational
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
+
-
DC24
X1.2 X1.1
Auxiliary power
X4.i1+
X4.i1-
Digital input
X4.i2+
X4.i2-
Digital output
X4.01
X4.01
X4.02
X4.02
+
-
+
-
-K1
For 3-pole non-automatic air circuit brea-
kers
(operational currents up to 4000 A/
conducting path)
1-pole,
2 parallel conducting
paths,
only with grounded-
neutral system
2-pole,
only with grounded-
neutral system
1-pole,
only with grounded-
neutral system
3WL Air Circuit Breakers
X5.2 X5.1
DIGmat S100
+
X2.1
-
X2.3
X4.03
X4.03
X4.04
X4.04
+
-
+
-
12
14
11
-X6.14 -X5.12
12
14
-K2
11
-F1
-X6.13 -X5.11
For 4-pole non-automatic air circuit breakers
(operational currents up to 4000 A/conducting path)
2-pole
1-pole,
3 parallel conducting paths,
only with grounded-neutral
system
1-pole,
2 parallel conducting paths,
only with grounded-neutral
system
2-pole,
only with grounded-neutral
system
current. If the parallel or series connection is made at a distance
of 1 m from the connecting bars, the circuit breaker can be used
at full operational current load.
]
Grounded-neutral system
Load
Project planning aids
+
Shunt
(60mV)
-
-Q01
1
3
5
SENTRON
3WL
-F3
-Q01 2
4
6
2-pole
2 parallel conducting
paths
2-pole
1-pole,
only with grounded-
neutral system
Siemens · 2009
57

Advertisement