6. INSTALLATION REQUIREMENTS
I I f f t t h h e e t t o o t t a a l l r r e e f f r r i i g g e e r r a a n n t t c c h h a a r r g g e e i i n n t t h h e e s s y y s s t t e e m m i i s s ≤1 1 . . 8 8 4 4 k k g g t t h h e e r r e e a a r r e e n n o o m m i i n n i i m m u u m m
s s u u r r f f a a c c e e r r e e q q u u i i r r e e m m e e n n t t s s . .
a
If the total refrigerant charge in the system is >1.84 kg it is necessary to comply with the minimum surface
requirements indicated in the following procedure:
1 calculate, based on piping length, the total refrigerant charge (mc)
2 calculate area room A (Aroom A)
3 calculate, through table 1, the maximum refrigerant charge allowed by room A (mmax)
4 i i f f m m m m a a x x ≥ m m c c t t h h e e u u n n i i t t c c a a n n b b e e i i n n s s t t a a l l l l e e d d i i n n r r o o o o m m A A
i i f f m m m m a a x x ≤ m m c c
1 calculate the area of room B adjacent to room A (Aroom B)
2 calculate, through table 2, the minimum total area (Amin total) required for the total refrigerant charge
(mc)
3 3 i i f f ( ( A A r r o o o o m m A A + + A A r r o o o o m m B B ) ) ≥ A A m m i i n n t t o o t t a a l l
4 calculate, through table 3.1 or 3.2, (depending on the power of the outdoor unit), the minimum area of
natural ventilation opening between room A and room B
5 the unit can be installed in room A if
There are 2 ventilation openings (permanently open) between room A and B, 1 at the top and 1 at the
bottom.
Lower opening: the lower opening must meet the minimum area requirements (VAmin). It must be as
close to the floor as possible. If the ventilation opening starts from the floor, the height should be
≥20mm. The lower part of the opening must be less than 100 mm from the floor. At least 50% of the
required opening area must be <200 mm from the floor. The entire area of the opening must be <300
mm from the floor.
Upper opening: the upper opening area must be greater than or equal to the lower opening. The lower
part of the upper opening must be at least 1.5 m above the upper part of the lower opening.
Outward ventilation openings are NOT considered suitable ventilation openings (the user can lock them
when it is cold).
i i f f ( ( A A r r o o o o m m A A + + A A r r o o o o m m B B ) ) < A A m m i i n n t t o o t t a a l l call the retailer
32
a Indoor unit
A Room where the unit is installed.
B Room adjacent to room A.
Area A+B must be greater than or equal
to the minimum surface required in table
2 according to the total charge.