Endress+Hauser Fieldbus levelflex M FMP 40 Operating Instructions Manual

Endress+Hauser Fieldbus levelflex M FMP 40 Operating Instructions Manual

Foundation fieldbus guided level-radar
Hide thumbs Also See for Fieldbus levelflex M FMP 40:
Table of Contents

Advertisement

Quick Links

BA 244F/00/en/02.03
Nr. 52011934
Valid as of software version:
V 01.02.00 (amplifier)
V 1.00 (communication)
levelflex M
FMP 40
Foundation Fieldbus
Guided Level-Radar
Operating Instructions
TM
F
TM

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Fieldbus levelflex M FMP 40

  • Page 1 levelflex M BA 244F/00/en/02.03 Nr. 52011934 FMP 40 Valid as of software version: V 01.02.00 (amplifier) V 1.00 (communication) Foundation Fieldbus Guided Level-Radar Operating Instructions...
  • Page 2 An overview of all device functions can be found on page 94. The operating manual BA 245F/00/en provides an extensive description of all device functions – Description of the device functions for Levelflex M, which can also be found on the enclosed CD-ROM. Endress+Hauser...
  • Page 3: Table Of Contents

    Cable specifications Foundation Fieldbus . . 30 Contact addresses of Endress+Hauser ..88 Connection data ..... . 30 Recommended connection .
  • Page 4: Safety Instructions

    "Ex documentation", which is an integral part of this Operating Manual. Strict compliance with the installation instructions and ratings as stated in this supplementary documentation is mandatory. • Ensure that all personnel are suitably qualified. • Observe the specifications in the certificate as well as national and local regulations. Endress+Hauser...
  • Page 5: Notes On Safety Conventions And Symbols

    A terminal which must be connected to earth ground prior to making any other connection to the equipment Equipotential connection (earth bonding) A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential line according to national or company practice Endress+Hauser...
  • Page 6: Identification

    2.1.1 Nameplate The following technical data are given on the instrument nameplate: Order No Designation according to Directive 94/9/EC (see Order Information) and designation of protection ENDRESS+HAUSER Made in Germany LEVELFLEX-M Serial number D-79689 Maulburg Order Code: Ser.-No.: IP68 / NEMA 6P...
  • Page 7 Special version Electronic insert / Communication B 2-wire, 4…20 mA HART D 2-wire, PROFIBUS-PA 2-wire, Foundation Fieldbus G 4-wire, 90...250 VAC, 4...20 mA HART H 4-wire, 10,5...32 VDC, 4...20 mA HART Special version FMP 40- Product designation (part 2) Endress+Hauser...
  • Page 8 B 3.1.B material, wetted parts SS316Ti, Inspection Certificate EN 10204, acc. specification 52005759 Y Special version FMP 40- Complete product designation ⇓ Please enter probe length in mm or inch / 0.1 inch inch / 0.1 inch probe length LN see page 12 Endress+Hauser...
  • Page 9: Scope Of Delivery

    "Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures". The instrument described in this manual thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the instrument by affixing to it the CE mark.
  • Page 10: Mounting

    ½ 1 " F12 housing Caution! Use only the threaded boss ??? AF 60 max. torque 20 Nm F12 or T12 housing ¾" AF 50 max. torque 5 Nm Endress+Hauser...
  • Page 11: Incoming Acceptance, Transport, Storage

    18 kg. Do not lift the measuring instrument by its probe rod in order to transport it. 3.2.3 Storage Pack the measuring instrument so that is protected against impacts for storage and transport. The original packing material provides the optimum protection for this. The permissible storage temperature is -40 °C…+80 °C. Endress+Hauser...
  • Page 12: Installation Conditions

    3 Mounting Levelflex M FMP 40 with Foundation Fieldbus Installation Conditions 3.3.1 Dimensions F12 housing T12 housing ca. 86 ENDRESS+HAUSER ENDRESS+HAUSER Levelflex-M Levelflex-M option: option: remote electronic distance sleeve 4 x Ø 8,5 Ø 60,3 Ø 76 Ø 76 Threaded connection Flange DN 40…200...
  • Page 13: Installation

    Coax probes can be shortened max. 80 mm from the end. They have centering units inside which fix the rod centrally in the pipe. The centerings are held with borders on the rod. Shortening is possible up to approx. 10 mm below the centering. Endress+Hauser...
  • Page 14 • Minimum distance of probe end to the container floor (C): – Rope probe: 150 mm – Rod probe: 100 mm – Coax probe: 50 mm • When installing outdoors, it is recommended that you use a protective cover (1) see »Accessories« on page 77.. Endress+Hauser...
  • Page 15 B Metal 100 mm for smooth walls Plastic 100 mm, min. 300 mm to metallic components outside of the tank Concrete 0.5 m/20", otherwise the max. possible measuring range is reduced Distance to protruding internals min. 300 mm. Endress+Hauser...
  • Page 16 – Rope probe: 150 mm – Rod probe: 100 mm – Coax probe: 30 mm It is better to order probes too long than too short since it is possible to shorten the probe if necessary. Endress+Hauser...
  • Page 17 Alternatively, the probe can also be installed into a pipe that must not protrude over the lower edge of the silo ceiling. Installation suggestions see diagram. ≥ 100 mm ≥ 100 mm metal Ø 80...150 mm Extension rod / Centering (see accessories) Endress+Hauser...
  • Page 18 12 m silo diameter 12 m silo diameter 9 m silo diameter 9 m silo diameter 6 m silo diameter 6 m silo diameter 3 m silo diameter 3 m level [m] level [m] Endress+Hauser...
  • Page 19 Observe the tensile strength of the probes or ensure that the tensile strength of the probes is not exceeded. Options for reducing the tensile forces: • Shorten the probe • If the maximum tensile load is exceeded, check whether it would be possible to use a non-contact ultrasonic device. Endress+Hauser...
  • Page 20 • Do not mount a rod or rope probe (1) exactly central when using metallic containers. Central mounting doesn‘t impair coax probe (2) performance. • When installing in tanks with a lot of internals or internals situated close to the probe: Use a coax probe. Endress+Hauser...
  • Page 21 • When installing a rod probe into a metallic pipe with internal diameter of up to 150 mm, you have all the advantages of a coax probe. • Welded joints that protrude up to approx. 5 mm/0.2" inwards do not influence measurement. Endress+Hauser...
  • Page 22 Measurement can be optimised by electronically tuning out interference echoes. • Bypass pipe and stilling well (only for liquids): for viscosities of up to 500 cst, a bypass pipe, stilling well or a coax probe can be used to prevent interference. Endress+Hauser...
  • Page 23 ≥ 1cm/m (1"/ 100") of the rope length. Reliable, earthed mounting Reliable, isolated mounting Mounting-kit isolated (see accessories) Mounting and contact with a bolt 4mm-rope: M14 6mm-rope: M20 Endress+Hauser...
  • Page 24 • There must not be any metallic reinforcement rings secured to the tank. • The wall thickness should be at Fibre-Glass Reinforced Plastic/PP < 15 mm. • There must be no open space between the tank wall and the probe. Endress+Hauser...
  • Page 25 With nozzle diameters of 200 204 mm mm / 8" or 250 mm / 10", therefore, a special flange with a “horn adaptor” must be fitted. Nozzles with nominal diameters greater than DN 250 / 10" should be avoided. DN200 (8") DN250 (10") Endress+Hauser...
  • Page 26 • Follow installation instructions on Page 14 ff.. • After mounting, the housing can be turned 350°, in order make access to the display and the connection compartment easier. • The max. measuring range is reduced to 34 m/1338". Ø 60,3 Ø 67 Endress+Hauser...
  • Page 27 Levelflex M FMP 40 with Foundation Fieldbus 3 Mounting Installation with separate housing • Follow installation instructions on Page 14 ff.. • Mount housing on a wall or pipe as shown in the diagram. wall ENDRESS+HAUSER Levelflex M 4 x Ø 8,5 ENDRESS+HAUSER Levelflex M pipe Ø...
  • Page 28: Post-Installation Check

    • Does the measuring instrument correspond to the measuring point specifications such as process temperature/pressure, ambient temperature, measuring range, etc.? • Are the measuring point number and labeling correct (visual check)? • Is the measuring instrument adequately protected against rain and direct sunlight (see page 77 ff.)? Endress+Hauser...
  • Page 29: Wiring

    Before connection please note the following: " Foundation Fieldbus devices are marked on the nameplate (1). The voltage is determined by the Foundation Fieldbus Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M standard and the desired safety concept. (e.g. FISCO). D-79689 Maulburg Order Code: Ser.-No.:...
  • Page 30: Cable Specifications Foundation Fieldbus

    4 Wiring Levelflex M FMP 40 with Foundation Fieldbus Wiring with M12 connector Before connection please note the following: " ENDRESS+HAUSER Made in Germany PROSONIC-M D-79689 Maulburg Foundation Fieldbus devices are marked on the Order Code: Ser.-No.: IP68 / NEMA 6P nameplate (1).
  • Page 31: Recommended Connection

    • Is the cable gland tight? • Is the Fieldbus connector screwed tight? • Is the housing cover screwed tight? • If auxiliary power is available: Is the instrument ready for operation and does the liquid crystal display show any value? Endress+Hauser...
  • Page 32: Operation

    4) Press to select the next function (e.g. "medium property (003)") 5) Press ) once return to previous function (e.g. "tank shape (002)") Press ) twice return to Group selection 6) Press ) to return to Measured value display Endress+Hauser...
  • Page 33 The third digit numbers the individual functions within the function group: • basic setup → • tank properties • medium property • process cond. … • Here after the position is always given in brackets (e.g. "tank properties" (002)) after the described function. Endress+Hauser...
  • Page 34: Display And Operating Elements

    Headline Position indicator ENDRESS + HAUSER Symbol Main value Unit – Selection list Function groups -> Functions HOME F000 F001 F002 F003 F004 ... FG00 FG01 FG02 Help text FG03 FG04 FG05 FG06 Envelope FG07 curve Fig. 4 Display Endress+Hauser...
  • Page 35 After a hardware lock, an operation of the instrument via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so. Tab. 2 Function of the keys Endress+Hauser...
  • Page 36: Local Operation

    It is not possible to unlock the hardware by communication. All parameters can de displayed even if the instrument is locked. ⇒ ⇓ press simultaneous ⇓ The LOCK_SYMBOL appears on the LCD. Endress+Hauser...
  • Page 37 There is no need to change these parameters under normal circumstances and conse- quently, they are protected by a special code known only to the E+H service organiza- tion. Please contact Endress+Hauser if you have any questions. Endress+Hauser...
  • Page 38 • sep. character (096) • end of probe (030) • unlock parameter (0A4) • level/ullage (040) • application par (0A8) • linearisation (041) • tag no (0C0) • customer unit (042) A complete “basic setup" (00) must be activated. Endress+Hauser...
  • Page 39: Display And Acknowledging Error Messages

    • The "diagnostics (0A)" function group can display current errors as well as the last errors that occurred. • If several current errors occur, use to page through the error messages. • The last occurring error can be deleted in the "diagnostics (0A)" function group with the function"clear last error" (0A2). Endress+Hauser...
  • Page 40: Foundation Fieldbus Communication

    5 Operation Levelflex M FMP 40 with Foundation Fieldbus Foundation Fieldbus communication 5.5.1 Synopsis There are two possibilities of connecting up a Foundation Fieldbus: Direct connection to a FF/H1 card Indirect connection via a linking device Endress+Hauser...
  • Page 41 SIM WP write protection SIM WP simulation Device identification Foundation Fieldbus identifies the device by its identification code and automatically allocates an appropriate field address. There is no separate hardware switch for this purpose. Endress+Hauser...
  • Page 42 • Download the device descriptions (.ffo and .sym files) to the directory offered. • When the configuration is complete, close the tool and the FF stack (if open). The Levelflex M device descriptions can be ordered direct from Endress+Hauser or downloaded from our website www.endress.com. They contain all data necessary to operate Endress+Hauser Foundation Fieldbus devices.
  • Page 43 Parameters that Primary value the process control system, describe the (main value) e.g. scaling, status device (calibration, linearisation etc.) Analog Input Function Block 2 parameters that are important to Secondary value the process control system, e.g. scaling, status (distance) Endress+Hauser...
  • Page 44 Shows any configuration, hardware, connection and system problems in the block. The cause of the alert is to be seen in the subcode field. The function of the resource block parameters not described here can can be taken from the Foundation Fieldbus specification, see www.fieldbus.org. Endress+Hauser...
  • Page 45 Thus, the calibration procedure via the display module (Chapter 6.4) is equally valid for a calibration via a network configuration tool. A complete list of the configuration parameters can be found in the "Description of Instrument Functions", BA 245F/00/en. Endress+Hauser...
  • Page 46 • System parameters • Lock TB Manufacturer parameters Most of these methods are identical to the respective function group in the operating menu. A detailed description of them can be found in the "Description of Instrument functions", BA 245F/00/en. Endress+Hauser...
  • Page 47: Mode_Blk

    PARSIMULATIONVALUELEVEL PARTANKPROPERTIES PARSIMULATIONVALUEVOLUME PARMEDIUMCONDITION PARALANGUAGE PARPROCESSPROPERTIES PARBACKTOHOME PARENDOFPROBE PARFORMATDISPLAYFT PAPROBESHORTENED PARNOOFDECIMALS PARPROBEFREE PARSEPARATIONCHARACTER PARPROBELENGTH PARACTUALERROR PARPROBELENGTHSETUP PARLASTERROR PAREMPTYCALIBRATION PARCLEARLASTERROR PARFULLCALIBRATION PARRESET PARECHOQUALITYFMP PAROPERATIONCODE PARCHECKDISTANCE PARMEASUREDDISTANCE PARSUPPRESIONDISTANCE PARMEASUREDLEVEL PARSTARTMAPPINGRECORD PARAPPLICATIONPARAMETER PARPRESMAPRANGE PARPROTSOFTVERSIONSTRING PARDELETEMAPPING PARDISTANCEUNIT PAROFFSETOFMEASUREDDISTANCE PARDOWNLOADMODE PAROUTPUTDAMPING PARABSMAXMESSDIST PARHIGHBLOCKINGDISTANCE PAREDITRANGEMAXSAMPLEDIST Endress+Hauser...
  • Page 48: E+H_Levelflex_M_Xxxxxxxx

    MODE_BLK = OOS then pressing the WRITE CHANGES button. Press the READ ALL button to check the values stored in the device. Normally operation is resumed as soon as MODE-BLK is set to AUTO. Endress+Hauser...
  • Page 49: Operation

    × FIELD_VAL --------------------------------------------------------------------------------------------------------- - XD_SCALE_MAX XD_SCALE_MIN – The L_TYPE parameter influences the signal conversion: • Direct: CHANNEL_VALUE • Indirect: FIELD_VALUE × --------------------------------------- - OUT_SCALE_MAX OUT_SCALE_MIN – OUT_SCALE_MIN • Indirect square root: FIELD_VALUE × --------------------------------------- - OUT_SCALE_MAX OUT_SCALE_MIN – OUT_SCALE_MIN Endress+Hauser...
  • Page 50 8 - 15 Critical alarms of increasing priority Alarm status Parameter Description HI_HI_ALM The status of the HI_HI alarm HI_ALM The status of the HI alarm LO_ALM The status of the LO alarm LO_LO_ALM The status of the LO_LO alarm Endress+Hauser...
  • Page 51 During simulation the transducer output value is substituted by the simulated value. A simulation is also possible by switching MODE_BLK to "MAN" and entering a value for OUT. Parameter Description SIMULATE Enables, sets and displays a simulated value, options: – enable/disable – simulated value – output value Endress+Hauser...
  • Page 52 – If appropriate, set the advisory and critical alarms. – Set MODE_BLK_TARGET to Auto. 5. Link the function blocks in the function block editor. 6. Download the configuration (menu configure). 7. If appropriate, check the configuration by using the SIMULATE function, see page 51 Endress+Hauser...
  • Page 53 View Objects Analog Input 2 Function Block 1510 View Objects PID Function Block 1515 View Objects Arithmetic Function Block 1520 View Objects Input Selector Function Block 1525 View Objects Signal Characterizer Function Block 1530 View Objects Integartor Function Block 1535 View Objects Transducer Block 1540 Endress+Hauser...
  • Page 54 Levelflex M FMP 40 with Foundation Fieldbus 5.5.10 Parameter access via ToF Tool The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle. It is used to support commissioning, securing of data, signal analysis and documentation of the instruments. It is compatible with the following operating systems: Win95, Win98, WinNT4.0, Win2000 and...
  • Page 55 Levelflex M FMP 40 with Foundation Fieldbus 5 Operation Signal analysis via envelope curve: Note! The Levelflex M can also be operated locally using the keys. If operation is prevented by the keys being locked locally, parameter entry via communication is not possible either. Endress+Hauser...
  • Page 56: Commissioning

    Select the basic unit (this message appears the first time the instrument is switched on) ⇓ The current measured value is displayed ⇓ After is pressed, you reach the group selection. This selection enables you to perform the basic setup Endress+Hauser...
  • Page 57: Basic Setup

    F = full calibr. (= span) UB = upper blocking distance setting in 006 setting in 059 D = distance (distance flange / product) SD = safety distance display in 0A5 setting in 015 = level LB = lower blocking display in 0A6 distance Endress+Hauser...
  • Page 58 EEPROM. " Caution! All functions are described in detail, as is the overview of the operating menu itself, in the manual “Description of the instrument functions – BA 245F”, which is a separate part of this operating manual. Endress+Hauser...
  • Page 59: Basic Setup With The Vu 331

    (see installation in plastic containers). When using a metallic surface at the process connection, the "standard" option is suffi- cient. Note! In principle the employment of a metallic surface area should be preferred at the pro- cess connection! Endress+Hauser...
  • Page 60 The lower group applies to very loose or loosened bulk solids. Reduction of the max. possible measuring range by means of: • extremely loose surfaces of bulk solids, e.g. bulk solids with low piled density when filled pneumatically. • Build-up, primarily of moist products. Endress+Hauser...
  • Page 61 Use this function to select the polarity of the probe end signal. If the probe end is uncovered or in an insulated attachment, there is a negative probe end signal. The signal from the probe end is positive if the attachment is grounded. Selection: • free • tie down isol. • tie down gnd. Endress+Hauser...
  • Page 62 With this function, the probe length can be determined automatically. Selection: • length ok • too short • too long After selection "length too short" or "length too long", the calculation of the new value need approx. 10 s. Endress+Hauser...
  • Page 63 E max = probe length – lower blocking distance Function "full calibr." (006) ⇒ This function is used to enter the distance from the minimum level to the maximum level (=span). 100% F = full calibration (= span) F max = E – upper blocking distance Endress+Hauser...
  • Page 64 1) The indicated blocking distances are prearised. At media with DK >7, the upper blocking distance UB can be reduced for rod- and rope probes on 0.1m. The upper blocking distance UB can be entered manually. Note! Within the upper and lower blocking distance, a reliable measurement can not be guaranteed. Endress+Hauser...
  • Page 65 • The range to be suppressed is suggested in the "range of mapping (052)" function Anyway, it is wise to carry out a mapping even in this case. Note! At free probe, the mapping should be confirmed with the choice "probe free". Endress+Hauser...
  • Page 66 For manual mapping, the default value is 0,3 m. Function "start mapping" (053) ⇒ This function is used to start the interference echo mapping up to the distance given in "range of mapping" (052). Selection: • off: no mapping is carried out • on: mapping is started Endress+Hauser...
  • Page 67: Blocking Distnace

    After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E)" function group) is recommended (see page 99). Blocking distnace Note! At installation in high nozzles, please the blocking distance in the function "upper block.dist" (059) newly enter! ⇒ Endress+Hauser...
  • Page 68: Envelope Curve With Vu 331

    ⇒ Note! If the envelope curve mode is active on the display, the measured values are updated in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has been optimised. Endress+Hauser...
  • Page 69: Function "Envelope Curve Display" (0E3)

    The active navigation mode is indicated by a symbol in the top left hand corner of the display. Horizontal Zoom mode: orizontal zoom in horizontal zoom out Move mode: oved to the left moved to the right Vertical Zoom mode: … - vertical zoom (4 steps) Endress+Hauser...
  • Page 70 • Press to exit the navigation. The set increases and shifts are retained. Only when you reactivate the "recording curve" (0E2) function does the Levelflex use the standard display again. ⇒ ⇓ After 3 s, the following message appears Endress+Hauser...
  • Page 71: Basic Setup With The Tof Tool

    • Status image • Enter the measuring point description (TAG number). Change to the next page Note! • Each parameter that is changed must be confirmed with the RETURN key! • The "Next" button moves you to the next screen display: Endress+Hauser...
  • Page 72 – medium properties (for a description, see page 60) – process properties(for a description, see page 61) Basic Setup step 3/6: • Enter the application parameters: – end of probe (for a description, see page 61) – probe length (for a description, see page 62) Endress+Hauser...
  • Page 73 – probe length (for a description, see page 62) – determine length (for a description, see page 62) Basic Setup step 5/6: • Enter the application parameters: – empty calibration (for a description, see page 63) – full calibration (for a description, see page 63) Endress+Hauser...
  • Page 74 • The measured distance and the current measured value are always displayed in the header • for a description, see page 65 measured value distance 6.8.1 Blocking distance Note! At installation in high nozzles, please the blocking distance in the function "upper block.dist" (059) newly enter! Endress+Hauser...
  • Page 75 For the optimization of the measurement the installation of the Levelflex in another place can be executed when enterference echoes. 6.8.3 User-specific applications (operation) For details of setting the parameters of user-specific applications, see separate documentation BA 245F/00/en - description of the instrument functions of the Levelflex M. Endress+Hauser...
  • Page 76: Maintenance

    They contain the related replacement instructions. All the spare parts kits which you can order from Endress+Hauser for repairs to the Levelflex M are listed with their order numbers on pages 86 and 87. sind alle Ersatzteil- Kits mit Bestellnummern aufgeführt, die Sie zur Reparatur des Levelflex M bei...
  • Page 77: Accessories

    Levelflex M FMP 40 with Foundation Fieldbus 8 Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A Weather protection cover made of stainless steel is available for outdoor mounting (order code: 543199-0001).
  • Page 78 DN50 / 2", inside diam. 50...57mm DN80, inside diam. 80...85mm 3", inside diam. 76...78mm DN100 / 4", inside diam. 100...110mm DN150 / 6", inside diam. 152...164mm DN200 / 8", inside diam. 201...215mm DN250 / 10", inside diam. 253...269mm Special version HMP40- complete product designation Endress+Hauser...
  • Page 79 In these cases the fixing must be reliably grounded (see page 23). Service adapter FXA 193 For communication with ToF Tool via the display connector. (Bestell-Nr.: 50095566). Commuwin II Operating software for intelligent instruments. Endress+Hauser...
  • Page 80 Alloy of Aluminium AL Si 12 Dimensions [mm] / [inch]: 122x150x80 (HxBxT) / 4.8x5.9x3.2 EMC version with conductive sealing Also suitable for use in zone 1, in combination with a Levelflex M with ATEX II 1/2 G EEx ia IIC T6 approval. Endress+Hauser...
  • Page 81: Trouble-Shooting

    Correct configuration Communication ok? Ready FXA 193 does not of COM port on PC function Contact E+H Service Instrument Not ok measures Check basic setup Repeat Measurement ok? Ready incorrectly basic setup Proceed according to section 'Trouble shooting’ in OM Endress+Hauser...
  • Page 82: System Error Messages

    A221 Probe pulse deviation HF module or cable between HF Check contacts on from average values module and electronics defective HF module If fault cannot be eliminated: Replace HF module Tab. 3 System error messages Endress+Hauser...
  • Page 83 - risk of as level leaves safety overspill distance; A671 linearisation ch1 not linearisation table is in edit mode activate linearisation table complete, not usable Tab. 3 System error messages Endress+Hauser...
  • Page 84: Application Errors

    Repeat once more empty calibr. (005). echo) after turn loss of echo the output is set to any initialisation phase to Caution! on the power value/current. high. Before conformation change with supply to the edit mode. Endress+Hauser...
  • Page 85 (slope rect. properties selected → error in the entire Calibration not possible. → 20 mA/100% measuring range) Selection → Select standard expected → Thresholds too high 2.) actual 1.) actual 4 mA/0% Medium properties Select lower medium properties. incorrect. Endress+Hauser...
  • Page 86: Spare Parts

    Gasket set 5201 0526 consist of: 2 gaskets 25 x 20.5 x 2 FA; Pos. 1 O-ring 49.21 x 3.53 EPDM; Pos. 1 O-ring 113.9 x 3.63 EPDM; Pos. 1 O-ring 72.0 x 3.0 EPDM probe rope probe rod Endress+Hauser...
  • Page 87 4 mm Probe rod 16 mm for 5201 3352 5201 3353 Probe rod 16 mm for complete probes with process connection 1½" process connection 1½" variants from the product max. length 4 m max. length 4 m structure list Endress+Hauser...
  • Page 88: Return

    (from OS 4.6) with Rev. 1, DD 1. Contact addresses of Endress+Hauser The addresses of Endress+Hauser are given on the back cover of this operating manual. If you have any questions, please do not hesitate to contact your E+H representative.
  • Page 89: Technical Data

    • Digital interface Auxiliary energy Electrical connection • Housing F 12 with additionally sealed terminal compartment for standard or EEx ia Cable entry see page 29 Supply voltage see page 30 ff. Power consumption min. 60 mW, max. 900 mW Endress+Hauser...
  • Page 90 Degree of protection • housing: IP 68, NEMA 4X (open housing: IP20, NEMA 1) • probe: IP 68 (NEMA 6P) Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20…2000 Hz, 1 (m/s²)²/Hz Cleaning of the probe see Technical Information TI 358F Endress+Hauser...
  • Page 91 Display see page 32 Certificates and approvals CE approval The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark. External standards and EN 60529 guidelines Protection class of housing (IP-code)
  • Page 92 10 Technical data Levelflex M FMP 40 with Foundation Fieldbus Supplementary Documentation Supplementary Docu- • System Information Levelflex (SI 030F/00/en) mentation • Technical Information (TI 358F/00/en) • Operating Instructions "Description of instrument functions" (BA 245F/00/en) Endress+Hauser...
  • Page 93 Levelflex M FMP 40 with Foundation Fieldbus 10 Technical data Endress+Hauser...
  • Page 94: Appendix

    + sw-no. serial no. Note! The default values of the parameters are typed in boldface. Endress+Hauser...
  • Page 95 2nd cyclic value select V0H0 distplay value measured value display value sim. off sim. level simulation value sim. volume sep. character display test . point , comma measured dist. measured level application par. not modified modified distance unit download mode Endress+Hauser...
  • Page 96: 11.2 Operating Matrix Foundation Fieldbus

    11 Appendix Levelflex M FMP 40 with Foundation Fieldbus 11.2 Operating matrix Foundation Fieldbus/ Commuwin II Endress+Hauser...
  • Page 97: 11.3 Description Of Functions

    Levelflex M FMP 40 with Foundation Fieldbus 11 Appendix 11.3 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation BA 245F/00/en - a description of the instrument functions of the Levelflex M. Endress+Hauser...
  • Page 98: 11.4 Function And System Design

    Reference point for "E" see above diagram, Details see page 57. The Levelflex possesses functions for the interference echo suppression that can be activated by the user. They guarantee that interference echoes from e.g. internals and struts are not interpreted as level echoes. Endress+Hauser...
  • Page 99 Level echoes are detected as positive signals in the envelope curve. Interference echoes can be both positive (e.g. reflections from internals) and negative (e.g. nozzles). The envelope curve, the map and the differential curve are used for the evaluation. Level echoes are searched for in the differential curve. Endress+Hauser...
  • Page 100 The level signal is then detected unequivocally as a positive sig- nal in the differential curve. For detecting the level echo, the amplitude must lie above the echo threshold. Negative probe end signal Launch pulse Envelope curve Mapping Differential curve = Envelope curve Mapping Endress+Hauser...
  • Page 101 • with display and operating module VU 331, • with a Personal Computer, FXA 193 and the operating software ToF Tool. The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro- impulse).
  • Page 102 EP 0 694 235 (under Licence) • US 5,517,198 (under Licence) • US 5,661,251 EP 0 780 664 • US 5,827,985 EP 0 780 664 • US 5,884,231 EP 0 780 665 • US 5,973,637 EP 0 928 974 Endress+Hauser...
  • Page 103: Index

    Lock ........36 Unlock parameter ......37 Endress+Hauser...
  • Page 104 Write protection ......41 Warning ........39 Endress+Hauser...
  • Page 105 Levelflex M FMP 40 with Foundation Fieldbus Index Endress+Hauser...
  • Page 106 Index Levelflex M FMP 40 with Foundation Fieldbus Endress+Hauser...
  • Page 107 I hereby certify that the returned equipment has been cleaned and decontaminated acc. to good industrial prac- tices and is in compliance with all regulations. This equipment poses no health or safety risks due to contamination. _______________________________ ___________________________________ (Date) (company stamp and legally binding signature) More information about services and repairs: www.services.endress.com Endress+Hauser...
  • Page 108 Belorgsintez Canada Philippines Poland Minsk Endress+Hauser Ltd. Endress+Hauser Philippines Inc. Endress+Hauser Polska Sp. z o.o. Tel. (0172) 263166, Fax (0172) 263111 Burlington, Ontario Metro Manila Warszawy Tel. (905) 6819292, Fax (905) 6819444 Tel. (2) 3723601-05, Fax (2) 4121944 Belgium / Luxembourg Tel.