The installation position should be selected with the following points in mind:
Leveling should be +/- 5 mm.
Pipework and electrical connections are readily accessible.
Ensure there are no obstructions in front of the condenser inlet.
It is recommended to have a clearance of at least 500mm between the condenser face and adjacent
wall or unit.
Where multiple units are to be installed in the same location, the contractor needs to consider each
individual case carefully.
Due care should be taken to avoid the discharge air from each unit adversely affecting other units in
the vicinity.
There can be many variations of unit quantities and available space and this manual does not cover all
such possible options. In general terms, air recirculation and local heat build up should be avoided at
all times.
Caution
The unit should never be installed adjacent to a dust source (such as a dirty road or extractor fan).
External contamination of the condenser fins lead to high condensing temperatures and will reduce
the life of the unit.