9 TERMS

This section explains some of the terms used in this manual.
Adaptor address (No. 0 set on Intelligent Controller, No. 1 to 7 set on communication
adaptors)
An adaptor address is the address assigned to an optional communication adaptor.
Link system address (No. 1 to 2, fi xed)
A link system is a collection of indoor units and outdoor units connected to a single inter-unit
control wire. Up to two link systems each can be connected to the Intelligent Controller and to
an optional communication adaptor.
Outdoor unit system address (No. 1 to 30 for each link system, set on outdoor unit side)
An outdoor unit system is collection consisting of one outdoor unit and the indoor units
connected to that outdoor unit. A single link system can contain up to 30 outdoor systems.
Indoor unit address
Up to 64 indoor units can be connected in one link system.
The Intelligent Controller system supports up to two link systems connected to the Intelligent
Controller only (128 indoor units), or four link systems (256 indoor units) when an optional
communication adaptor is connected.
Indoor unit addresses, central control addresses, and unit names are applied to indoor units.
• Indoor unit address (No.1 to 64 / for each outdoor unit system, set on indoor unit side)
An indoor unit address is a unique number within an outdoor unit system.
These numbers are assigned to each indoor unit, including units subject to group control.
These numbers are the smallest unit of totals calculation and distribution calculation.
• Central control address (No.1 to 64 for each link system, set on Intelligent Controller and
other central control equipment)
A central control address is a unique number within a link system. It is shared with other
central control equipment (system controllers, multi controllers, etc.)
This is the same address used in group control.
• Unit name (set on Intelligent Controller)
This is the same name used in group control.
It is the smallest unit of operation, monitoring, and timer operations.
Distribution group number (No. 1 to 8, set on Intelligent Controller)
A distribution group is made up of one or more tenants. The total of the distribution ratios in
the group is 100%. The Intelligent Controller system supports up to 8 distribution groups. GHP,
PAC, and HOT units cannot be mixed in a single distribution group.
Tenant number (No. 1 to 256 set on Intelligent Controller)
A tenant is a collection that is the object of distribution calculations (or operation and
monitoring). It is made up of one or more indoor units. The system as a whole supports up to
256 tenants.
Zone number (No. 1 to 128, set on Intelligent Controller)
A zone is unrelated to distribution. It is a range for performing all-unit operation, monitoring,
and timer operation. GHP, PAC, and HOT units can be mixed in a zone. The system as a
whole supports up to 128 zones.