MSC4000 - MSC15000 USER MANUAL
Drain Settings
Drain type (M)
Set to "None" if using pneumatic drains.
Set to "Level" if using solenoid demand float drains.
Autotest Time (M) – Set the time (between 30 to 1440 minutes) between Autotest cycles for drains which use a drain
level switch. This will force the drain to open automatically regardless of whether the drain switch is closed or not.
Drain Cycle Interval (M) – Set the number of seconds between drain opening for drains which are running in Timed
Drain mode.
Drain On Duration (M) – Set the number of seconds that the drain will remain open per drain cycle while for drains
which are running in Timed Drain mode.
Note: Level drains which experience a drain fault will automatically switch to timed drain mode using the duration
and interval times. Clearing the alarm will switch the drain back to level drain mode.
M
Supervisor level access required