Honeywell Notifier AM12-24 Manual page 10

Conventional fire panel
Table of Contents

Advertisement

CN0 terminals
Terminal #
CN0
1
ALARM Relay NO-NC
2
ALARM Relay Common
3
FAULT Relay NO-NC
4
FAULT Relay Common
5
SOUNDER (–)
(shown polarity, normal condition)
SOUNDER (+)
6
(shown polarity, normal condition)
7
TX
8
RX
9
GND
10
+ 24Vdc 1A User
11
12
GND User
13
14
Auxiliary input (External power supply Fault indication)
15
Auxiliary input (level 2 access )
16
Auxiliary input (Evacuation)
17
Auxiliary input (Technical Alarm)
CN1 terminals
Terminal # CN1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PAGINA - 8
NOTIFIER ITALIA
Description
Description
Line 1 - (GND)
Line 2 - (GND)
Line 3 - (GND)
Line 4 - (GND)
Line 5 - (GND)
Line 6 - (GND)
Line 7 - (GND)
Line 8 - (GND)
Line 9 - (GND)
Line 10 - (GND)
Line 11 - (GND)
Line 12 - (GND)
Line 1 +
Line 2 +
Line 3 +
Line 4 +
Line 5 +
Line 6 +
Line 7 +
Line 8 +
Line 9 +
Line 10 +
Line 11 +
Line 12 +
Installation and programming manual
Doc. M-124.1-AM1224-ENG Rev A.1
Note
Max 2A resistive 30Vdc,
Contact NO-NC selectable via
JALL Jumper
Max 2A resistive 30Vdc
Contact NO-NC selectable via
JGST Jumper
Protected with 1A Fuse
Total current: 1A (Sounder+User )
End of Line resistor: 47K 5%
RS232 serial interface input
(used for UPLOAD)
Protected with 1A Fuse
Total current: 1A ( Sounder+User )
End of Line resistor 2k7 ohm 5% 1/4W
Note
End of Line resistor
2k7 ohm 5% 1/4W
AM-1224
AM-1224_manu