Installation - Lennox Allied Air A93UH1E Installation Instructions Manual

Warm air gas furnace upflow/horizontal left and right air discharge
Table of Contents

Advertisement

Installation

Setting Equipment
Do not connect the return air ducts to the back of the
furnace. Doing so will adversely affect the operation of
the safety control devices, which could result in personal
injury or death.
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into
living space resulting in personal injury or death.
Upflow Applications
The gas furnaces can be installed as shipped in the upflow
position. Refer to Figure 13 for clearances. Select a location
that allows for the required clearances that are listed on
the unit nameplate. Also consider gas supply connections,
electrical supply, vent connection, condensate trap and
drain connections, and installation and service clearances
[24 inches (610 mm) at unit front]. The unit must be level
from side to side. Tilt the unit slightly (maximum 1/2 in.
from level) from back to front to aid in the draining of the
heat exchanger. See Figure 12.
Page 10 of 55
WARNING
WARNING
Tilt the unit slightly (Max. 1/2") from back to front to aid in the draining of the heat exchanger.
Unit must be level side-to-side in all applications.
Figure 12. Setting Equipment
Allow for clearances to combustible materials as indicated
on the unit nameplate.
Improper installation of the furnace can result in
personal injury or death. Combustion and flue products
must never be allowed to enter the return air system or
air in the living space. Use sheet metal screws and joint
tape to seal return air system to furnace.
In platform installations with furnace return, the furnace
should be sealed airtight to the return air plenum. A door
must never be used as a portion of the return air duct
system. The base must provide a stable support and an
airtight seal to the furnace. Allow absolutely no sagging,
cracks, gaps, etc.
For no reason should return and supply air duct systems
ever be connected to or from other heating devices
such as a fireplace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property
damage could result.
Return Air Guidelines
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Issue 1922
WARNING
507867-02