Lennox Allied Air A93UH1E Installation Instructions Manual page 19

Warm air gas furnace upflow/horizontal left and right air discharge
Table of Contents

Advertisement

A93UH1E & 92G1UHE Maximum Allowable Intake or Exhaust Vent Length in Feet
1-1/2" Pipe
Number of
Capacity
90° Elbows
Used
030 /
070
045
1
25
20
2
20
15
3
15
10
4
10
5
6
7
n/a
n/a
8
9
10
1-1/2" Pipe
Number of
Capacity
90° Elbows
Used
030 /
070
045
1
20
15
2
15
10
3
10
4
5
6
n/a
7
n/a
8
9
10
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
507867-02
Standard Termination at Elevation 0 - 10,000 ft
2" Pipe
Capacity
030 /
090
110
070
045
76
61
71
56
66
51
61
46
56
41
n/a
n/a
51
36
46
31
41
26
36
21
31
16
Concentric Termination Elevation 0 - 10,000 ft
2" Pipe
Capacity
030 /
090
110
070
045
68
53
63
48
58
43
53
38
48
33
n/a
n/a
43
28
38
23
33
18
28
13
23
8
2-1/2" Pipe
Capacity
030 /
090
110
070
045
39
19
110
95
34
14
105
90
29
9
100
85
24
95
80
19
90
75
14
85
70
9
80
65
n/a
75
60
70
55
n/a
65
50
2-1/2" Pipe
Capacity
030 /
090
110
070
045
37
17
100
85
32
12
95
80
27
7
90
75
22
85
70
17
80
65
12
75
60
7
n/a
70
55
65
50
n/a
60
45
55
40
Table 5.
Issue 1922
3" Pipe
Capacity
030 /
090
110
070
045
63
38
132
132
58
33
127
127
53
28
122
122
48
23
117
117
43
18
112
112
38
13
107
107
33
8
102
102
28
97
97
23
92
92
n/a
18
87
87
3" Pipe
Capacity
030 /
090
110
070
045
59
34
116
116
54
29
111
111
49
24
106
106
44
19
101
101
39
14
96
96
34
9
91
91
29
86
86
24
81
81
n/a
19
76
76
14
71
71
090
110
113
113
108
108
103
103
98
98
93
93
88
88
83
83
78
78
73
73
68
68
090
110
109
109
104
104
99
99
94
94
89
89
84
84
79
79
74
74
69
69
64
64
Page 19 of 55