  • Page 1 Installation & Operation Manual Stationary Filters Bag Filter Dust Collector S-SERIES ELECTRICAL Installation, Wiring, and Troubleshooting No portion of this manual may be reproduced without the written approval of Nederman. Original Installation and Service Manual 2022-06-03 – Rev 3.1...
  • Page 2: Table Of Contents

    ELECTRICAL INSTALLATION, WIRING AND TROUBLESHOOTING TABLE OF CONTENTS Section 1.0 ….Preface..……………………………………….………………………….………. 3 Section 2.0…..Circuit Sizing………….……………………………………………………..3-4 Section 3.0..Motor Connections ................... 6 Section 4.0..Trouble Shooting ..................7-8 Section 5.0..Inrush Current ..................... 9 Wiring Diagrams ......................10-11 Nederman Customer Service & Technical Support techsupport.us@nedermen.com +1 (336) 821-0800...
  • Page 3: Section 1.0

    There are specific electrical codes and standards outlined within this manual that need to be employed when making the electrical connections. Failure to adhere to the procedures outlined in this document WILL VOID the Nederman product warranty. Section 2.0 – Circuit Sizing ‐...
  • Page 4 Branch circuit protection to be sized at 300% motor FLC for Nontime‐Delay fuse (Class CC fuses) on tables 430.52, 430.248, and 430.250. Based on 2020 NEC 70 Article 430 and best‐practice. Recommended setting for overload on Nederman Push Button Starters based on motor nameplate multiplied by service factor.
  • Page 5 Product Owner/End-user shall provide branch circuit protection. Refer to the Motor Circuit Sizing Tables on previous pages for max breaker and fuse sizes. *Note: F1 represents fuses. An Inverse Time Breaker would replace the fuses (F1) in the below example. Nederman Customer Service & Technical Support techsupport.us@nedermen.com +1 (336) 821-0800...
  • Page 6: Section 3.0

    Per NFPA 79, 13.5.9, wire‐nuts and soldering motor leads are unacceptable connection methods for motors as their use greatly increases the risk of fire and hazards to machinery and personnel. The use of wire‐nuts on Nederman motors VOIDS THE WARRANTY! WARNING Figure 1 –...
  • Page 7: Section 4.0

    The voltage label will be 200‐240v (for 208v, 230v, & 240v) or 440‐480v (for 460v and 480v) 6) Does the motor spin freely by hand? If not, there is a problem with the motor. Contact Nederman to order a replacement. 7) Is ductwork connected? Ensure that all ductwork is connected to the fan.
  • Page 8 Section 4.0 – Troubleshooting Please follow these steps to verify motor condition. If it is a brand new motor, please contact Nederman. 1) Separate the individual motor leads and check the resistance if each winding with an ohmmeter. A standard multi‐meter is limited in checking issues with motors, but can still provide some valuable information.
  • Page 9: Section 5.0

    Below is an example of an adjustable trip class. Trip Class 2 < Ti ≥ 10 4 < Ti ≥ 10 6 < Ti ≥ 20 0.5 < Ti ≥ 30 Nederman Customer Service & Technical Support techsupport.us@nedermen.com +1 (336) 821-0800...
  • Page 10: Wiring Diagrams

    The group’s offering covers the design stage through installation, commissioning and servicing with subsidiaries in 29 countries and agents and distributors in over 30 countries. Nederman is ISO 9001 and 14001 certified and develops and produces in its own manufacturing and assembly facilities in Europe, North America and Asia.