SYMPTOM
POSSIBLE CAUSES
Gate opens, but will
a. Open control active
not close with
b. Vehicle loop detector active
transmitter or
c. Loss of AC power with AC FAIL set to
Timer-to-Close.
OPEN
d. Low battery with LOW BATT set to OPEN
e. Fire dept input active
f. Timer-to-Close not set
g. Close entrapment protection device active
Gate closes, but
a. Vehicle loop detector active
will not open.
b. Low battery with LOW BATT option set to
CLOSE
Exit loop activation
a. Exit vehicle detector setup incorrectly
does not cause gate
b. Inoperable exit loop detector
to open.
c. Low battery with LOW BATT option set to
CLOSE
Interrupt loop does
a. Vehicle detector setup incorrectly
not cause gate to
b. Inoperable vehicle loop detector
stop and reverse.
c. Anti-tail set to ON
Shadow loop does
a. Vehicle detector setup incorrectly
not keep gate at
b. Inoperable vehicle loop detector
open limit.
Obstruction in
a. Force adjustment needed
gate's path does not
cause gate to stop
and reverse.
Photoelectric
a. Incorrect photoelectric sensor wiring
sensor does not
b. Inoperable photoelectric sensor
stop or reverse
gate.
Edge sensor does
a. Incorrect edge sensor wiring
not stop or reverse
b. Inoperable edge sensor
gate.
Alarm sounds for 5
a. Double entrapment occurred (two
minutes or alarm
obstructions within a single activation)
sounds with a
command.
Alarm beeps three
a. Low battery
times with a
command.
Alarm beeps when
a. Expansion board setting
running.
b. Constant pressure to open or close is
given
Expansion board
a. Inoperable control board to expansion
function not
board wiring
controlling gate.
b. Incorrect input wiring to expansion board
c. Inoperable expansion board or inoperable
control board
TROUBLESHOOTING
SOLUTIONS
a. Check all open inputs for an active input
b. Check all vehicle detector inputs for an active detector
c. Check AC power and AC Fail option setting
d. Check if AC power is available. If no AC power, then running on
batteries and battery voltage must be 23 Vdc or higher. Charge
batteries by AC or solar power or replace batteries.
e. Check Fire Dept input
f. Check Timer-to-Close (TTC) setting
g. Check all entrapment protection device inputs for an active sensor
a. Check all vehicle detector inputs for an active detector
b. Check if AC power is available. If no AC power, then running on
batteries and battery voltage must be 23 VDC or higher. Charge
batteries by AC or solar power or replace batteries.
a. Review exit loop detector settings. Adjust settings as needed.
b. Replace inoperable exit loop detector.
c. Check if AC power is available. If no AC power, then running on
batteries and battery voltage must be 23 VDC or higher. Charge
batteries by AC or solar power or replace batteries.
a. Review Interrupt loop detector settings. Adjust settings as needed.
b. Replace inoperable Interrupt loop detector.
c. Set anti-tail to OFF.
a. Review shadow loop detector settings. Adjust settings as needed.
b. Replace inoperable shadow loop detector.
a. Refer to the Adjustment section to conduct the obstruction test and
perform the proper force adjustment that is needed.
a. Check photoelectric sensor wiring. Retest that obstructing
photoelectric sensor causes moving gate to stop, and may reverse
direction.
b. Replace inoperable photoelectric sensor. Retest that obstructing
photoelectric sensor causes moving gate to stop, and may reverse
direction.
a. Check edge sensor wiring. Retest that activating edge sensor causes
moving gate to stop and reverse direction.
b. Replace inoperable edge sensor. Retest that activating edge sensor
causes moving gate to stop and reverse direction.
a. Check for cause of entrapment (obstruction) detection and correct.
Press the reset button to shut off alarm and reset the operator.
a. Check if AC power is available. If no AC power, then running on
batteries and battery voltage must be 23 Vdc or higher. Charge
batteries by AC or solar power or replace batteries
a. Pre-warning is set to "ON"
b. Constant pressure to open or close is given
a. Check control board to expansion board wiring. If required, replace
wire cable.
b. Check wiring to all inputs on expansion board.
c. Replace inoperable expansion board or control board.
41