Accessories: Flaring piping kit
CZ-3F5, 7AEN

SELECT THE BEST LOCATION

INDOOR UNIT
- There should not be any heat source or steam near the unit.
- There should not be any obstacles blocking the air circulation.
- A place where air circulation in the room is good.
- A place where drainage can be easily done.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or
other obstacles.
- Indoor unit of this room air conditioner shall be installed on the
wall in a height of at least 2.3 m.
OUTDOOR UNIT
- If an awning is built over the unit to prevent direct sunlight or rain,
be careful that heat radiation from the condenser is not obstructed.
- There should not be any animal or plant which could be affected by
hot air discharged.
- Keep the spaces indicated by arrows from wall, ceiling, fence or
other obstacles.
- Do not place any obstacles which may cause a short circuit of the
discharged air.
- If piping length is over the common length, additional refrigerant
should be added as shown in the table.
Piping size
Model
Gas Liquid
A73KR/A93KR 3/8"
A123KR
1/2"
Indoor/Outdoor unit installation diagram
Max.
Common
Elevation
Length
(m)
1/4"
7.5
5
1/4"
7.5
5
Max.
Additional
Piping
Refrigerant
Length
(g/m)
(m)
10
20
15
20
45