- When compressor stops (reaches room temperature), outdoor fan
will operate for 30 seconds.
(30 seconds Forced Operation).
Hot Start Control
When Heating operation starts, Indoor Fan will not start until the
indoor heat exchanger reaches 30°C as diagram shown.
Hot Start is completed when indoor heat exchanger reaches 39°C.
Anti Cold Draft Control
- This operation is to prevent the Cold Draft during Heating mode
operation.
- The operation will start when compressor OFF (Thermo OFF)
during Heating operation.
- For the first 30 sec from compressor OFF (Thermo OFF), Indoor fan
speed will operate accordingly to the Indoor heat exchanger
temperature as shown below: