Daikin FWW Series Technical Manual page 27

Chilled water fan coil units
Hide thumbs Also See for FWW Series:
Table of Contents

Advertisement

Application Information
Others
The controller board of 4 pipes system (W3) comes with other dry contact options.
L
COMP
TRANSFORMER
i)
Unoccupied Mode
If the dry contact is closed, the Unoccupied mode is activated and vice versa. When Timer On is active,
system goes back to Occupied mode.
ii) Anti Freeze Mode
Anti Freeze operation has the highest priority among all unit operation. Anti Freeze operation will be
activated only if dry contact is closed and vice versa.
iii) Window Open Mode
If the dry contact is closed, Window Open Mode will be activated on the fan coil unit which is connected and
vice versa.
Note: The dry contact connection point can be connected with individual fan coil unit only. It cannot be connected
parallel with other fan coil units.
Cable Size
Model
Power supply cable size*
Number of wire
Recommended fuse*
Model
Power supply cable size*
Number of wire
Recommended fuse*
Model
Power supply cable size*
Number of wire
Recommended fuse*
Model
Power supply cable size*
Number of wire
Recommended fuse*
Important: * These values are for information only. They should be checked and selected to comply local
or national codes and regulations. They are also subjected to the type of installation and size of
conductor
Unit
mm2
A
Unit
FWC03C
mm2
1.5
3
A
1
Unit
FWC09C
mm2
1.5
3
A
3
Unit
FWC10FD
mm2
1.5
5
A
3
FWE / FWF / FWK / FWW
1.5
3
2
FWC04C
1.5
3
1
FWC11/12/14/16C
FWC02/03/04/05FD
1.5
3
5
FWC-G
FUD20/25B
1.0
5
6
Unoccupied Mode
Anti Freeze Mode
Window Open Mode
FWC06C
FWC07C
1.5
1.5
3
3
1
2
FWC06/08FD
1.5
1.5
5
5
1
2
FUD30/40B
1.5
1.5
3
4
10
10
23