Daikin FWW Series Technical Manual page 112

Chilled water fan coil units
Hide thumbs Also See for FWW Series:
Table of Contents

Advertisement

Engineering Data - Chilled Water Fan Coil Unit
MODEL
NOMINAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL HEATING CAPACITY
(ENTERING WATER TEMP. = 50°C)
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
AIR DISCHARGE
CONTROL
OPERATION
HIGH
MEDIUM
AIR FLOW
LOW
QUIET
NOMINAL WATER FLOW RATE
HEAD LOSS (COOLING)
HEAD LOSS (HEATING) : 50°C
MAX. WORKING PRESSURE
SURFACE AIR VELOCITY
SOUND PRESSURE LEVEL (H/M/L/Q)
UNIT DIMENSION - (WITH PANEL)
PACKING DIMENSION - (PANEL)
UNIT WEIGHT (UNIT + PANEL)
CONDENSATE DRAIN SIZE
PIPE CONNECTION
TYPE
DRIVE
FAN SPEED
FAN
FAN EFFICIENCY
TYPE
INDEX OF PROTECTION (IP)
INSULATION GRADE
RATED INPUT
POWER
RATED RUNNING
FAN MOTOR
CURRENT
STARTING CURRENT
MOTOR OUTPUT
MOTOR EFFICIENCY
POLES
MATERIAL
TUBE
DIAMETER
MATERIAL
COIL
FIN
FACE AREA
ROW
WATER VOLUME
TYPE
AIR
FILTER
QUALITY
QUANTITY
CASING
MODE
ENTERING AIR TEMPERATURE
ENTERING WATER TEMPERATURE
LEAVING WATER TEMPERATURE
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
108
FWK06E
Btu/h
21000
W
6150
Btu/h
16700
W
4890
Btu/h
28000
W
8210
W
95
A
0.44
V/Ph/Hz
CFM
750
CFM
620
CFM
480
CFM
320
USGPM
4.71
litres/min
17.83
kPa
20
kPa
19
kPa
m/s
0.92
dBA
42 / 38 / 32 / 23
H X W X D
mm
H X W X D
mm
kg
26 + 4
mm
mm
HIGH
RPM
530
MEDIUM
RPM
450
LOW
RPM
360
HIGH
%
57.10
MEDIUM
%
60.50
LOW
%
58.20
HIGH
W
95
MEDIUM
W
79
LOW
W
67
HIGH
A
0.44
MEDIUM
A
0.40
LOW
A
0.36
A
0.44
W
30
HIGH
%
35.20
MEDIUM
%
25.60
LOW
%
15.60
mm
m
0.39
2
2
litre
1.36
pc
COLOUR
COOLING
HEATING
27°C DB / 19°C WB
20°C DB
50°C (2 Pipes System)
7°C
12°C
FWK08E
FWK09E
25000
30000
7330
8790
19200
22300
5630
6540
33600
38300
9850
11230
126
167
0.55
0.74
220-240/1/50
4 WAY AUTOMATIC LOUVER (UP & DOWN)
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
860
890
700
720
540
570
380
420
5.59
6.69
21.17
25.29
37
22
33
19
1608
1.05
1.13
46 / 42 / 35 / 27
48 / 43 / 38 / 30
265 x 820 x 820 (340 x 990 x 990)
341 x 916 x 916 (125 x 1020 x 1020)
26 + 4
28 + 4
19.05
19.05 BSP FEMALE THREAD ADAPTOR
TURBO FAN
DIRECT
600
660
500
550
400
450
60.50
65.00
62.10
63.00
63.30
52.70
PERMANENT SPLIT CAPACITOR (INDUCTION)
IP20
126
167
103
109
89
86
0.55
0.74
0.45
0.49
0.39
0.39
0.71
0.89
45
65
37.70
30.80
25.20
24.10
14.60
21.50
8
COPPER
7.00
ALUMINIUM
0.39
0.37
2
1.34
1.97
WASHABLE SARANET FILTER
WHITE
-
-
Engineering & Physical Data
FWK11E
FWK13E
38000
11140
27400
8030
45500
13340
186
0.85
1000
840
680
540
8.45
31.94
44
38
1.02
50 / 47 / 43 / 33
52 / 49 / 45 / 39
300 x 820 x 820 (375 x 990 x 990)
376 x 916 x 916 (125 x 1020 x 1020)
32 + 4
710
610
510
58.30
57.20
58.40
B
186
151
118
0.85
0.71
0.57
1.02
80
40.30
31.00
23.20
6
0.46
3
3
2.35
1
43000
12600
31000
9090
52000
15240
227
1.03
1140
1000
840
700
9.60
36.29
53
47
1.17
32 + 4
800
710
610
55.70
65.40
61.60
227
176
144
1.03
0.82
0.69
1.28
110
48.50
40.60
30.90
0.46
3
2.35

Advertisement

Table of Contents
loading

Table of Contents