Model: FWE08/10/12E
Standard Mounting
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger
rods (wall mounting bracket for floor standing), and check for its alignment with the unit. Also, check that
the hangers are secured and the base of the fan coil unit is leveled in both horizontal directions, taking into
account the gradient for drainage flow as recommended in Figure A.
Figure A
Please ensure that the following steps are taken:
• Unit installation should be tilted at least 10mm as recommended in Figure A.
• The drain pipe slope shall be kept at least 1:100.
• Provide clearance for easy servicing and optimal air flow as shown in Figure B.
• The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm
return air.
• Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must be a large distance away from the door.
Figure B
Washer
Washer
16
Nut
Nut
400mm or more
Hanger Bracket
Indoor Unit
250mm or less
300mm
(Min.)
Floor Standing Type
Application Information
Ceiling
Drainage Pipe
Utensils, furnitures or built-in
architectural features must not
protrude more than 250mm
Floor
1m or more