Safety Compliance And Hazardous Locations Standards - National Instruments NI-9269 Getting Started

Hide thumbs Also See for NI-9269:
Table of Contents

Advertisement

Caution
intended hazardous (classified) location, having a tool secured cover/door,
where a minimum protection of at least IP54 is provided.
Special Conditions for Hazardous Locations Use in Europe and
Internationally
The NI 9269 has been evaluated as Ex nA IIC T4 Gc equipment under
DEMKO 07ATEX 0626664X and is IECEx UL 14.0089X certified. Each NI 9269 is marked
II 3G and is suitable for use in Zone 2 hazardous locations, in ambient
temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI 9269 in Gas Group IIC
hazardous locations, you must use the device in an NI chassis that has been
evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
Caution
exceeding 140% of the peak rated voltage value of 85 V at the supply
terminals to the equipment.
Caution
Pollution Degree 2, as defined in IEC/EN 60664-1.
Caution
enclosure with a minimum ingress protection rating of at least IP54 as
defined in IEC/EN 60079-15.
Caution
use of a tool.

Safety Compliance and Hazardous Locations Standards

This product is designed to meet the requirements of the following electrical
equipment safety standards for measurement, control, and laboratory use:
IEC 61010-1, EN 61010-1
6
ni.com
The system must be installed in an enclosure certified for the
Transient protection shall be provided that is set at a level not
The system shall only be used in an area of not more than
The system shall be mounted in an ATEX/IECEx-certified
The enclosure must have a door or cover accessible only by the
NI-9269 Getting Started