Temperature Pointer (Items Vp And Vv) - Honeywell Enraf VITO Instruction Manual

Table of Contents

Advertisement

___________________________________________________________________________

3.4.3 Temperature pointer (items VP and VV)

By means of the value pointer (item VP) a vector can be loaded to the HCU or ICU_HPI option board. Next, with
item VV, the selected data is returned. Item VP consists of 4 positions, in the middle separated by a '.' or ',' :
v w . x y (or v w , x y). The values for the value pointer are listed in table 3 – 2 together with the obtained data.
v w
,
x y
Selected data
0 0
,
0 0
HCU / ICU_HPI Emulation & Function
Emulation: MPU, HSU, HPU, HCU
Function:
0 0
,
0 1
Configuration boot code
Sales code option: C
0 0
,
0 2
HCU / ICU_HPI hardware version
0 0
,
0 3
Boot code software version
0 2
,
0 0
Calculated temperature of 1
0 2
,
0 1
Calculated temperature of 2
:
:
0 2
,
1 3
Calculated temperature of 14
0 2
,
2 6
Standard deviation
0 2
,
2 9
Calculated I_ref
0 2
,
8 2
Calculated resistance 1
0 2
,
8 3
Calculated resistance 2
:
:
0 2
,
9 5
Calculated resistance 14
0 3
,
0 1
Error counters HART addresses 3, 4 and 5
(762 VITO MRT Interface has HART address 5)
0 3
,
0 9
Detected HART device addresses
0 3
,
1 0
Initial detected VITO device type & software version
Description:
0 3
,
1 1
Real active functions of VITO Interface (refer to description of VP=03,10)
0 3
,
1 2
Actual executed HART commands from 762 VITO Interface
Table 3 – 2
Item
Name
VP=
Temperature value pointer
VV
Temperature pointer value
Instruction manual VITO
Average temperature measurement with MRT
HC:
HART channel installed
AO:
analog output
ST:
spot temperature
MR:
VITO average MRT/multi spot probe
WS:
external water bottom probe
PR:
pressure transmitters
boot code: 0A
J
2E
W
1A
X
12
Y
3F
st
element
nd
element
:
th
element
st
element
nd
element
:
th
element
763 :
762 VITO MRT/multiple RTD interface
MRT :
MRT element
10 :
software version 1.0
Description
Temperature value pointer; format: 2 digits, separator, 2 digits
(refer to table 3 – 2).
Example:
VP=02.00: value pointer loaded to request the
calculated temperature of the 1
Temperature pointer value.
This item holds the value requested by item VP
(refer to table 3 – 2).
Example:
the requested temperature of the 1
(standard floating point format).
Example / Dimension
VV=HCU HCAOMR- - PR
VV=HCU CONFIG: 3F
VV=HW VERSION: 00
VV=BOOTSW VERS:01
(floating point format)
according to item TD
according to item TD
(floating point format)
(floating point format)
according to item TD
(floating point format)
< 0.5E-10
(floating point format)
1.0275 mA ±0.05
(floating point format)
(floating point format)
(floating point format)
VV=0000:0000:0013
(5 for VITO Interface)
VV= - - - - 5 - - - - - - - - -
VV=763 MRT
st
element.
10
st
element
Page 26

Advertisement

Table of Contents
loading

Table of Contents