Troubleshooting; Temperature Error Request Hcu/Hpi (Item Em); Temperature Status Request (Item Mq) - Honeywell Enraf VITO Instruction Manual

Table of Contents

Advertisement

___________________________________________________________________________
3.4

Troubleshooting

3.4.1

Temperature error request HCU/HPI (item EM)

This item helps you configuring correctly by showing the most recent temperature error encountered by the option
board.
xx00
No error
xx50
Element 1 detected absent
xx51
Element 2 detected absent
xx52
Element 3 detected absent
xx53
Element 4 detected absent
xx54
Element 5 detected absent
xx55
Element 6 detected absent
xx56
Element 7 detected absent
xx57
Element 8 detected absent
xx58
Element 9 detected absent
xx59
Element 10 detected absent
xx60
Element 11 detected absent
xx61
Element 12 detected absent
xx62
Element 13 detected absent
xx63
Element 14 detected absent
xx
22 for MPU emulation
24 for HPU emulation
30 for HCU emulation
3.4.2

Temperature status request (item MQ)

Four bytes status information (B0 B1 B2 B3) with the following meaning:
For decoding of the status bytes, refer to the ASCII table in appendix A.
Status byte 0:
Contains the characters '0' ÷ 'D', indicating the highest submersed element of the MRT. At start up this is: 'I'.
Status byte 1:
Bit 0: general temperature fail
1: fail in average product temperature
2: fail in average gas temperature
3: level exceeds lowest element
4: level exceeds highest element
5: element fail (one or more elements defect)
6: 1
7: 0
Status byte 3:
Bit 0: no previous store command
1: alternative (lower) element selected
2÷5: 0
6: 1
7: 0
Note:
Only the bits which are set to '1' have an active status.
Instruction manual VITO
Average temperature measurement with MRT
xx70
Sub-system error. Check or replace VITO Interface board
xx72
Not supported element type. Check item MT
xx73
Wrong element configuration. Check item MN
xx80
R_test error (out of limits)
xx81
R_cable error (out of limits) or isolation resistance to ground too low
xx84
Standard deviation too high or isolation resistance to ground too low
xx91
Wrong J0 .. JD setting. Check these items.
xx92
No data available. Check wiring or connection with VITO Interface
Status byte 2:
Bit 0: last valid level used
1: manual level used
2: 0
3: 0
4: 0
5: 0
6: 1
7: 0
Page 25