9-9-9. Manual Adjustment Function of Outside Temperature (TO) Sensor
This function is provided to fix TO sensor value manually by the switch operation on the interface P.C. board in
the outdoor unit. When the unit stops abnormally due to TO sensor failure, etc, an emergent operation is
available by setting up the value manually to position near the current outside temperature.
[Operation]
(1) Set the rotary switches on the interface P.C. board to numbers as follows:
• SW01/SW02/SW03 to [2/1/15]
• 7-segment display: [ t o ]
(2) Keep pressing the push-switch SW04 on the interface P.C. board for 1 second or more. The mode changes
to the TO sensor value fix manual mode.
(3) Pressing the push-switch SW04 increases the setting temperature and pressing the SW05 decreases the
setting temperature. Set the temperature to any values.
[Clear]
Return SW01/SW02/SW03 on the interface P.C. board in the outdoor unit to [1/1/1].
NOTE) If operated with TO sensor fixed by this function, the system control operation of the air conditioner may
not be based on the specification of the product. Therefore an emergent operation should be restricted
to a day or so.
When the outside temperature is 45ºC or more, set to 45ºC (SW02="9")
<Service support function list>
SW01
SW02
SW03
1
2
3
4
2
1
5
6
7
9
11
16
2
3
1~16
2
1~16
4~7
1~16
2
15
1
2
3
4
16
1 to 16
5
6
7
8
SW01
SW02
SW03
1
1
1
7-segment display [A]
[J . C]
[J . H]
[P . ]
[A . 1]
[C . ]
[H . ]
[C . H]
[F . ]
[r . d]
[E . r]
[H . r]
[F . d]
[t . o]
[01] to [16]
[17] to [32]
[33] to [48]
[49] to [64]
[65] to [80]
[81] to [96]
[97] to [112]
[113] to [128]
7-segment display [A/B]
[U 1] [ E28 ]
Refrigerant circuit and control communication line check function (Cooling
operation)
Refrigerant circuit and control communication line check function (Heating
operation)
Indoor PMV forced full open function
Indoor remote controller discriminating function
Cooling test operation function
Heating test operation function
Indoor collective start/stop (ON/OFF) function
Fan test operation function
Outdoor refrigerant recovery operation function (Reclaim function)
Check code clear function
Solenoid valve forced open/close function
Fan forced operation function
Outside temperature sensor manual adjustment function
Indoor No. 1 to 16
Indoor No. 17 to 32
Indoor No. 33 to 48
Indoor No. 49 to 64
Indoor No. 65 to 80
Indoor No. 81 to 96
Indoor No. 97 to 112
Indoor No. 113 to 128
Follower unit check code / Corresponding unit fan operation function
– 88 –
Function contents
Set number of SW02
Set number of SW02 + 16
Set number of SW02 + 32
Set number of SW02 + 48
Set number of SW02 + 64
Set number of SW02 + 80
Set number of SW02 + 96
Set number of SW02 + 112
Function contents

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents