Toshiba SMMS-u MMY-MUP0801HT8 Quick Reference page 47

Super modular multi system
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
1∗: Fan P.C.
board 1
P22
P22
2∗: Fan P.C.
board 2
1∗: Compressor
1 side
2∗: Compressor
2 side
P26
P26
1∗: Compressor
1 side
P29
P29
2∗: Compressor
2 side
P31
Check codes Detected by Central Control Device
Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
C05
C06
C12
Differs according to
nature of alarm-causing
trouble
P30
(L20 displayed.)
Location
Description
of
detection
Fan INV.
Outdoor fan
P.C. board
P.C. board
trouble
Compressor
IPM,
P.C. board
Compressor
shortcircuit
protection
trouble
Compressor
Compressor
P.C. board
position
detection circuit
trouble
Indoor unit
Other indoor
trouble
(group follower
unit trouble)
Location
Description
of
detection
Central
Central control
control
device
device
transmission
trouble
Central
Central control
control
device reception
device
trouble
General-
Batch alarm
purpose
for general-
device
purpose
I/F
device
control interface
Central
Group control
control
follower unit
device
trouble
Duplicated
central control
address
Check code detection
System status
condition(s)
All stop
Protected operation of Fan
inverter P.C. board
All stop
Overcurrent is momentarily
detected during startup of
compressor.
All stop
Position detection is not
going on normally.
Stop of
There is trouble in other
corresponding
indoor unit in group,
unit
resulting in detection of
E07/L07/L03/L08.
Check code detection
System status
condition(s)
Continued
Central control device is
operation
unable to transmit signal.
Continued
Central control device is
operation
unable to receive signal.
Continued
Trouble signal is input to
operation
control interface for general-
purpose devices.
Continued
Trouble occurs in follower
operation
unit under group control.
([P30] is displayed on central
control remote controller.)
Continued
There is duplication in
operation
central control addresses.
– 47 –
Check items (locations)
• Check fan motor.
• Check for failure in fan
P.C. board.
• Check connection of fan
motor connector.
• Check power voltage of
the main power supply.
• Check connector
connection and wiring on
compressor P.C. board.
• Check for failure in
compressor (layer
shortcircuit).
• Check for failure in outdoor
P.C. board ( Compressor).
• Check wiring and
connector connection.
• Check for compressor
layer short-circuit.
• Check for failure in
compressor P.C. board.
• Check indoor P.C. board.
Check items (locations)
• Check for failure in central
control device.
• Check for failure in central
control communication line.
• Check termination
resistance setting.
• Check for failure in central
control device.
• Check for failure in central
control communication line.
• Check terminator resistor
setting.
• Check power supply for
devices at other end of
central control
communication line.
• Check failure in P.C.
boards of devices at other
end of central control
communication line.
• Check trouble input.
• Check check code of unit
that has generated alarm.
• Check address settings.

Hide quick links: