Outdoor Unit Function Code No. (O. DN) Table (Includes Functions Needed to Perform Applied Control on Site)
DN
Item
003
Type Setting
004
7-segment Display Contents
Control
005
Prohibition/Permission of the NFC
Setting
007
Compressor Maintenance Period
Time
008
Operation Mode Selection Control
009
Capacity / Power Demand Control
00A
Power consumption upper limit
standard value setting
Heating (For power demand)_High
00b
Power consumption upper limit
standard value setting
Heating (For power demand)_Low
00C
Power consumption upper limit
standard value setting
Cooling (For power demand)_High
00d
Power consumption upper limit
standard value setting
Cooling (For power demand)_Low
00E
Setting Value during Demand
Control
00F
Setting value during Demand
Control (Expansion 1)
010
Setting Value during Demand
Control (Expansion 2)
012
Optional Output Setting Control 1
(CN514)
018
Priority Operation Mode Setting
019
Outdoor Fan High Static
Pressure Shift
01A
Operation standby
Heating standby
01d
System cooperation
defrosting settings 1
(number cooperating)
01E
System cooperation
defrosting settings 2
(zone address)
01F
System cooperation
defrosting settings 3
(cooperation address)
03d
Existence of Automatic Back Up
03F
Operation Control during Overflow
Detection of Indoor Unit
040
Operation Control during Outside
Abnormal Input Switching control
in receiving [L30][L02] from indoor)
082
Communication setting
Code range : 0000 to 0255
Type setting
0
DN Code [03]
0000
* DN Code [003] = 0000 : Undefined
0000 : Outdoor unit No.
0000 : Allow Wave Tool Advance test operation within 48 hours elapsed from the
outdoor unit power on time.
0001 : Regardless of the elapsed time, WTA cannot start test operation.
0002 : Regardless of the elapsed time, WTA can start test operation.
0000 : 0h
0000 : Non-selected Indoor units keep stand-by state (thermostat OFF).
0001 : Changing non-selected indoor units t the mode selected
0000 : Capacity demand
Code range
[0A] [0C] : 0000 to 0255
(1 kW to 255 kW)
[0B] [0D] : 0000 to 0099
(0.00 kW to 0.99 kW)
Setting Value during Demand Control for demand standard specifications can be set
with DN code [00E]. Its value for expansion specifications can be set in two steps
(DN codes [00F], [010]) during the normal operation and demand control (setting
value DN Code [00E]).
Demand control
[00E]
100%
0
95%
1
90%
2
85%
3
80%
4
75%
5
70%
6
65%
7
60%
8
55%
9
50%
10
–
11 to 14
0%
15 (Factory default)
0000 : Compressor Operation Output
0000 : Priority heating
0002 : Priority operation unit No.
0000 : Usual
0000 : None
0000 : None (vassal)
0002 : 2-system cooperation (master unit)
* set [01D] = 0002 or 0003 to outdoor unit set to master unit in outdoor DN code [01F]
0000 : None
0001 when not using central controller for control for system cooperation defrosting,
0001 to 0128 when using central controller
0000: None
0002 or 0003: Vassal units 2 or 3
0000 : Provided
0000 : System abnormal stop
0000 : System continuous operation
(Stop the corresponding indoor unit.)
0000: TCC-Link
Description
1
0001
0002
0001 : Start priority number
0001 to 0063
(1000 h to 63000 h)
0001 : Power demand
Power consumption upper
limit standard value
Heating
Cooling
No power demand function
0.01 kW
0.02 kW
10.00 kW
30.50 kW
DN Code
[00F]
0
1
2
3
4
4 (Factory default)
5
6
7
8 (Factory default)
9
10
11 to 14
15
0001 : Operating Rate Output
0001 : Priority cooling
0004 : Priority indoor unit
0001 : High Static Pressure Operation
0001 : Stanby
0001 : Prohibition
0003 :
3-system cooperation (master unit)
0001 to 0128: Addresses
0001: Master unit
0001 : Not provided
0001 : System continuous operation
(Stop the corresponding indoor unit.)
0001 : System abnormal stop
0003 : TU2C-Link
– 22 –
At shipment
According to type
2
0000 : Outdoor
unit No.
0000 : Allow
WTA test
operation
0000 : 0h
0000 : Non
Priority
0000 : Non
Priority
0000 : 0kW
DN Code
[00A]
[00B]
0000 : 0kW
[00C]
[00D]
0000
0000
0000 : 0kW
0000
0001
0000
0002
0010
0000
0000 : 0kW
0030
0050
0015 : 0%
(Forcedly stop)
[010]
0
0008 : 60%
1
2
3
5
6
7
0004 : 80%
8
9
10
11 to 14
15
0000 :
Compressor
Operation Output
0000 : Priority
heating
0000 : Usual
0000 : None
0000: None
(vassal)
0000: None
0000 : None
0000 : Provided
0000 : System
abnormal stop
0000 : System
continuous
operation
(Stop the
corresponding
indoor unit.)
0000: TCC-Link