Push-Button Operation - Siemens OpenAir GEB Series Manual

Hide thumbs Also See for OpenAir GEB Series:
Table of Contents

Advertisement

HMI (Human-Machine Interface)

Push-button operation

Activity
Display current address
(starting with lowest address digit)
Turn bus termination on / off
Enter Modbus address with push-
button
Enter push-button addressing
mode
(for use with Climatix
controllers)
Reset to factory settings
LED colors and patterns
Color
Green
Orange / green
Orange
Red
Blue
A6V101037253_en--_a
2017-02-17
Push-button operation
Press button < 1s
turn on 1. press 3x
2. press 1x shortly
3. press button until LED shines red
4. release button
turn off 1. press 3x
2. press button until LED shines red
3. release button
Press button > 1s and < 5s
1. Press button > 5s and < 10s
2. Release button
TM
Press button > 10s
Pattern
1s on / 5s off
flashing
1s orange / 1s green
1s on / 1s off
1s on / 5s off
Steady
1s on / 5s off
0.1s on / 1s off
Flashes 1x after address display
Confirmation
1-digits: red
10-digits: green
100-digits: orange
If termination is switched on, LED
flashes 1x blue after address display
Example:
124 = 4x red, 2x green, 1x orange
LED flashing and flickering stops
(termination mode)
LED flashes 1x blue
LED shines red (confirmation)
LED off
Address display
LED flashes 1x blue after address
display
Normal operation
LED flashing and flickering stops
(termination mode)
LED shines red (confirmation)
Normal operation
See chapter 'Push-button addressing '
below
LED shines red and gets dark after 5s
LED shines orange
LED flashes orange
Description
Normal operation ("life pulse") without bus traffic
Normal operation ("life pulse") with bus traffic
Device is in override control
Bus parameters not yet configured
Backup mode entered
Mechanical fault, device jammed or manual override
Internal error
Invalid configuration, e.g. Min = Max
Bus termination is set active.