Bradford White FVIR Defender Safety System RG240T6N394264475 Installation/Operation Instruction Manual page 25

Gas-fired water heater
Table of Contents

Advertisement

Troubleshooting Chart – Honeywell V1 continued-
LED Status
Five flashes and
three second
pause
Six flashes and
three second
pause
Seven flashes
and three second
pause
Eight flashes and
three second
pause
Control Status
Temperature sensor
fault.
Water leak detected
by accessory
module (some
models).
Gas valve electronic
fault detected.
False pilot flame
present.
Probable Cause
1. Damage to the temperature
wire.
2. Temperature sensor
resistance out of range.
3. Replace temperature sensor.
4. If temperature sensor
replacement does not correct
the problem; verify control is
not wet or physically
damaged.
5. Turn set point knob to "OFF"
position. Turn set point knob
to "PILOT" position and light
pilot.
6. Replace gas valve if five flash
error persists.
Excessive amount of water in
drain pan/water dam.
1. Verify control is not wet or
physically damaged.
2. Turn set point knob to "OFF"
position. Turn set point knob
to "PILOT" position and light
pilot.
3. Replace gas valve if seven
flash error persists.
1. Pilot valve stuck in open
position.
2. Turn set point knob to "OFF"
position. Turn set point knob
to "PILOT" position and light
pilot.
3. Replace gas valve if eight
flash error persists.
25