10

Test run

Before test run
• Before turning on the power supply, carry out the
following procedure.
1) By using insulation tester (500VMΩ), check that
resistance of 1MΩ or more exists between the
terminal block L to N and the earth (grounding).
If resistance of less than 1MΩ is detected, do not
run the unit.
2) Check the valve of the outdoor unit being opened
fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
Execute a test run
Operate the unit with the remote controller as usual.
For the procedure of the operation, refer to the
attached Owner's Manual to the outdoor unit.
A forced test run can be executed in the following
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
Wired remote controller
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
1
Push and hold OFF timer button and [ ]
setting button simultaneously for 10 seconds
or more. [TEST] is displayed on the display
part and the test run is permitted.
2
Push ON/OFF button.
3
Push menu button to select the operation
mode. Select [
Cool] or [
Heat] with
[ ] [ ] setting button, and then push menu
button (three times) again to determine the
operation mode.
• Do not run the air conditioner in a mode other
than [Cool] or [Heat].
• The temperature setting function does notwork
during test run.
• The check code is displayed as usual.
4
After the test run, push OFF timer button to
stop a test run.
([TEST] disappears on the display and the air
conditioner enters the normal stop mode.)
Wireless remote controller
1
Turn on the power of the air conditioner.
When power is turned on for the fi rst time
after installation, it takes approx. 5 minutes
until the remote controller becomes available.
In the case of subsequent power-on, it takes
approx. 1 minute until the remote controller
becomes available. Execute a test run after the
predetermined time has passed.
2
Push "ON/OFF" button on the remote
controller, select [
Cool] or [
Heat] with
"MODE" button, and then select
[
HIGH] with "FAN" button.
– 21 –
3
Cooling test run
Heating test run
Set the temperature
Set the temperature
to 17°C with the temp.
to 30°C with the temp.
setup buttons.
setup buttons.
4
Cooling test run
Heating test run
After confi rming a signal
After confi rming a signal
receiving sound "beep"
receiving sound "beep"
immediately set the
immediately set the
temperature to 18°C with
temperature to 29°C with
the temp. setup buttons.
the temp. setup buttons.
5
Cooling test run
Heating test run
After confi rming a signal
After confi rming a signal
receiving sound "beep"
receiving sound "beep"
immediately set the
immediately set the
temperature to 17°C with
temperature to 30°C with
the temp. setup buttons.
the temp. setup buttons.
6
4
5
Repeat procedures
Indicators "Operation" (green), "Timer"
(green), and "Ready" (orange) in the wireless
receiver section fl ash in approx. 10 seconds,
and the air conditioner starts operation. If
any of these indicators does not fl ash, repeat
2
5
procedures
to
.
7
Upon completion of the test run, push
"ON/OFF" button to stop operation.
<Overview of test run operations using the wireless
remote controller>
▼ Cooling test run:
ON/OFF → 17°C → 18°C → 17°C → 18°C → 17°C→
18°C → 17°C → (test run) → ON/OFF
▼ Heating test run:
ON/OFF → 30°C → 29°C → 30°C → 29°C → 30°C→
29°C → 30°C → (test run) → ON/OFF
Wired remote controller
1
When TEMPORARY button is pushed for 10
seconds or more, "Pi!" sound is heard and the
operation changes to test run. After approx. 3
minutes, a cooling operation starts forcedly.
Check cool air starts blowing. If the operation
does not start, check wiring again.
2
To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor
units in test run.
When a test run is not
4
5
.
performed properly
When a test run is not performed properly, refer
to the error code and the part to be checked on
"Troubleshooting".
When a test run is executed before installing the
external duct, a protection control may be activated
and lets the unit stop and the code P12 may be
displayed. (This is not due to a malfunction but to the
current control function of the DC motor in this unit.)
When a test run executed before installing the
external duct, select "Low" for the fan speed level or
cover the air discharge.
In addition, stop the operation before replacing the
High-effi ciency fi lter or opening the service panel.
After the test run, reset the circuit breaker of the
indoor unit.
TEMPORARY button