Toshiba RAV-HM561BTP-E Installation Manual page 19

Hide thumbs Also See for RAV-HM561BTP-E:
Table of Contents

Advertisement

2
Each time [ ] [ ] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs. The
indoor unit can be confi rmed for which to change
settings.
3
Push OFF timer button to confi rm the selected
indoor unit.
Code No.
Set data
4
Push the menu button to make Code No.
[
] fl ash. Change Code No. [
] with
[ ] [ ] setting button.
5
Push the menu button to make Set data
[
] fl ash. Change Set data [
] with
[ ] [ ] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
• To change other settings of the selected indoor
4
unit, repeat from Procedure
.
7
When all the settings have been completed,
push ON/OFF button to determine the settings.
"
" fl ashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is fl ashing.)
• To change settings of another indoor unit, repeat
1
from Procedure
.
External static pressure
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
1
2
3
4
5
6
procedure (
).
4
Specify [5d] to the CODE No. in procedure
.
5
For the SET DATA of procedure
, select a SET
DATA of the external static pressure to be set up
from the following table.
<Change on wired remote controller>
HM561, 801BTP series
SET DATA
External static pressure
0000
30 Pa
Factory setting
0001
50 Pa
0002
40 Pa
0003
100 Pa
0004
65 Pa
0005
120 Pa
0006
150 Pa
HM901, 1101BTP series
SET DATA
External static pressure
0000
40 Pa
Factory setting
0001
30 Pa
0002
50 Pa
0003
100 Pa
0004
65 Pa
0005
120 Pa
0006
150 Pa
HM1401, 1601BTP series
SET DATA
External static pressure
0000
50 Pa
Factory setting
0001
30 Pa
0002
40 Pa
0003
100 Pa
0004
65 Pa
0005
120 Pa
0006
150 Pa
The list above is when SW501-1 and SW501-2 is OFF.
External static pressure
When using the wireless remote controller
To set up the external static pressure, use the DIP
switch on the circuit board of the wireless reception
part.
For details, refer to the instruction manual of the
wireless remote controller kit. Alternatively, use the
switch on the indoor micro computer circuit board as
shown in the following figure and table.
* Once switched, the settings "0001", "0003", and
"0006" can be changed, but to reset to "0000",
you need to set the switch to the normal (default)
position and use a separately-sold wired remote
controller to overwrite the data with "0000".
SW501-1
OFF
ON
SW501-2
OFF
OFF
SET DATA
0000
0001
To reset to the factory default
Switch off SW501-1 and SW501-2, connect a
separately-sold
wired remote controller, and then perform the procedure
for installing a separately-sold filter on this page to set the
[5d] data to "0000"
– 18 –
Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
4
5
(
For the CODE No. in Procedure
For the [SET DATA] in Procedure
DATA of filter sign term from the following table.
SET DATA
0000
0001
0002
0003
OFF
ON
0004
ON
ON
0003
0006
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
(
For the CODE No. in Procedure
For the SET DATA in Procedure
DATA of shift value of detection temperature to be
set up from the following table.
SET DATA
Detection temperature shift value
0000
0001
0002
0003
0004
0005
0006
6
).
4
, specify [01].
5
, select the SET
Filter sign term
None
150 H
2500 H
(Factory default)
5000 H
10000 H
6
).
4
, specify [06].
5
, select the SET
No shift
+1°C
+2°C
(Factory default)
+3°C
+4°C
+5°C
+6°C