Table 2: Installer Configuration Menu (Part 5 of 5)
Parameter
Description and Default
Appearing
on Display
Comp/aux
Sets the mode of interaction
between the heat pump and the
auxiliary heat.
Default: off
1.
When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
2.
When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press
and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
3.
When the outdoor air sensor is not connected or it has a short, the thermostat bypasses heating lockout, cooling lockout,
high balance point, and low balance point. Emergency mode bypasses heating lockout and permits auxiliary heating
whenever a heating demand occurs.

Operation

Programming/Operating the TEC2102-3
Thermostat
Once the thermostat is configured via the Installer
Configuration Menu, its operating parameters can be
programmed via the Main User Menu. Access this
menu by pressing the MENU key during normal
thermostat operation. The Main User Menu contains
the basic operating features of the thermostat.
The Main User Menu also uses Auto Help, which is
displayed automatically in the menu when there is a
pause in programming activity. To exit Auto Help,
continue with the programming selection. When the
thermostat is in the Main User Menu and is left
unattended for 45 seconds, the menu reverts to the
Status Display Menu.
Enabling Override Schedule
Note: Enabling Override Schedule only appears when
in the Unoccupied Mode.
The override schedule prompt only appears when the
thermostat is in the unoccupied state. This menu
selection gives the user the option of overriding the
unoccupied setpoints with the occupied setpoints for
the amount of time specified under the TOccTime
parameter. See the Configuring the TEC2102-3
Thermostat section.
Note: If one of the digital inputs is configured to
operate as a remote override contact, this menu is
disabled.
TEC2102-3 N2 Networked Heat Pump Thermostat Installation Instructions
Selection Options
(on) – in the heating mode only: If the heat pump is not able to
satisfy the heating setpoint, the auxiliary heat is energized and the
heat pump is shut off. This typically applies when the air handler
heat pump coil is installed after the auxiliary heat. There is a
2-minute delay to restart the heat pump after the auxiliary heat is
shut down.
(off) – in the heating mode only: If the heat pump is not able to
satisfy the heating setpoint, the auxiliary heat is energized at the
same time as the heat pump stage. This typically applies when the
air handler heat pump coil is installed before the auxiliary heat (all
electric systems).
To override the unoccupied state while in the Main User
Menu:
1. Press the NO key to all prompts until the Override
Schedule prompt appears. If the thermostat is in
the unoccupied state, this is the first prompt.
2. Press the YES key to enable the temporary
override. The thermostat returns to the Status
Display Menu.
When scrolling through the Status Display Menu,
Override now appears for the occupancy status
parameter.
Resuming the Programmed Schedule
This menu only appears when the thermostat is in the
unoccupied override mode.
To resume the schedule while in the Main User Menu:
1. Press the NO key to all prompts until the Cancel
ovrd Y/N prompt appears. If the thermostat is in the
unoccupied override state, this is the first prompt.
2. Press the YES key to resume the programmed
schedule.
The thermostat returns to the Status Display Menu.
Entering Permanent Temperature Setpoints
The first prompt appearing in the Main User Menu of
the thermostat when in the occupied state is to set the
permanent temperature setpoint.
13