Chapter 2
Recommended terminals for wiring
• The following ferrule terminals are recommended for
signal cable for easy wiring and improved reliability of
connectivity.
Ferrule terminal with sleeves
Power cable size
2
mm
(AWG)
0.25 (24)
0.34 (22)
0.5 (20)
0.75 (18)
*) Manufacturer: Phoenix Contact
Wiring procedure
1. Push the gray part on the control circuit terminal block
into the socket with a slotted screwdriver (with a wide
of 2.5mm or less). (Insertion hole will open)
2. Insert the wire or ferrule terminal into the wire
insertion hole (round) while pressing the gray part with
a slotted screwdriver.
3. The wire is connected when release the screw driver.
2.5mm
Ferrule terminal
L1 [mm]
model*
AI 0,25-8YE
8
AI 0,34-8TQ
8
AI 0,5-8WH
8
AI 0,75-8GY
8
Push the gray part into
the socket with a slotted
screwdriver
φ
L2 [mm]
d [mm]
12.5
0.8
12.5
0.8
14
1.1
14
1.3
Crimping tool: CRIMPFOX UD 6-4 or CRIMPFOX ZA 3
• Even for pulling out the wire from the socket, press the
gray part with a slotted screwdriver (the insertion hole
will be opened while pressing).
Insert the wire
2-18
Installation and Wiring
φ
D [mm]
2.0
2.0
2.5
2.8
The wire is connected
when release the screw
driver