Placing the heating system in operation
TM
Checking the AquaSmart
30. Check operation of the maximum AquaSmart
that it switches the boiler off as soon as the boiler temperature set
TM
on the AquaSmart
is reached. Record the result in the
commissioning report ( page 23).
TM
– Set the AquaSmart
to the desired setting.
– Replace the front wall of the boiler ( Section 5.6, page 14).
Fig. 28 Checking temperature control
[1]
Adjustment keypad
6.6

Shutting off gas supply to boiler

▶ Set the room thermostats to the lowest setting.
▶ Disconnect the heating system from the power supply before
carrying out maintenance work.
▶ Turn the gas valve ON/OFF knob ( Fig. 26 [1]) clockwise to the
OFF position. Do not use excessive force.
6.7
Inform owner/operator, hand over technical
documentation
▶ Familiarize the owner/operator with the entire heating system and
the operating instructions for the boiler.
▶ Hand over the technical documentation to the owner/operator.
▶ Jointly sign the commissioning report.