5
Boiler installation
5.4
Fuel gas supply connection
Heed the following points for connecting the fuel supply:
▶ Work on gas components may be carried out only by
qualified and authorized personnel.
▶ Observe the local regulations or else the requirements
the National Fuel Gas Code, ANSI Z 223.1 when
connecting the gas supply. In Canada, the
requirements of CAN/CSA-B.149.1 and 2, Installation
Guidelines, must be observed.
▶ A manual shutoff valve must be installed outside the
boiler casing if required by the local code. We
recommend installing a manual shutoff valve in the
main gas pipe to the boiler.
▶ The gas pipes must be fastened outside the boiler.
5.4.1
Installing gas feed
For details of the required gas pipe diameter, refer to Tab. 7 and Tab. 8
on page 12. Make absolutely sure that the pipe fittings have the correct
thread size.
▶ Install a sediment trap at the inlet where the gas supply pipe connects
to the boiler.
The gas supply pipe is designed for a gas connection on
the right side. For conversion to a left-side gas
connection, see Section 5.1.
To prevent strain on the gas valves, extensions of the gas
supply line must be supported.
Pipe length
[foot] (1 foot = 0.3 m)
10
20
30
40
50
75
100
150
Table 7 Gas pipe supply volume
1) Maximum flow rate in cu ft/hr [ft3/h] based on a gas specific gravity of 0.60 and a gas pressure of 0.5 psi (34.5 mbar) or less and a pressure drop equivalent to a water column
of 0.3 inches (7.6 mm).
Iron pipe nominal diameter
[inch]
1
1¼
1½
2
2½
Table 8 Equivalent lengths for pipe fittings
12
Flow rate
1"
1¼ "
520
1060
350
730
285
590
245
500
215
440
175
360
160
305
120
250
Equivalent lengths for pipe fittings [feet] (1 foot = 0.3 m)
90 ° elbow
3
4
5
7
8
Fig. 11 Gas valve pipe connection
[1]
Gas supply
[2]
Manual shutoff valve
[3]
Sediment trap
[4]
Unions on the gas supply line (on site)
1)
3
3
[ft
/h] (1 ft
/h = 28.3 l/h)
1½ "
1600
1100
890
760
670
545
480
380
Pipe fitting type
T-piece
Shutoff valve
5
6
7
10
12
Logano G234X – 6 720 811 233 (2017/02)
1
2
3
4
6 720 806 028-07.1T
2"
2½ "
3050
4800
2100
3300
1650
2700
1450
2300
1270
2000
1020
1650
870
1400
710
1130
Gas shutoff
0.6
1.60
0.8
2.15
1.0
2.50
1.3
3.00
1.6
3.50