Insulation thickness
Take the following into account when determining the insulation
thickness:
Piping
Mode
Liquid piping
Refrigeration
Air conditioner
Gas piping
Refrigeration
Air conditioner
Depending on your local weather conditions, you may need to
increase the thickness of the insulation. If the ambient temperature
exceeds 30°C and the humidity exceeds 80%.
▪ Increase the thickness of the liquid piping with ≥5 mm.
▪ Increase the thickness of the gas piping with ≥20 mm.
Insulation sealing
To prevent rain and condensed water entering the unit, add a
sealing between the insulation and the front panel of the unit.
b
a
a
a
b
a
a
Sealing material
b
Front panel
14
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
14.1

About electrical compliance

This equipment (LRYEN10A7Y1 and LRNUN5A7Y1) complies with:
▪ EN/IEC 61000‑3‑11 provided that the system impedance Z
less than or equal to Z
at the interface point between the user's
max
supply and the public system.
▪ EN/IEC
61000‑3‑11
=
Standard setting the limits for voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems for
equipment with rated current ≤75 A.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a system impedance Z
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit and capacity up unit
4P605461-1B – 2020.08
Minimum
temperature during
operation
0°C
20°C
–20°C
0°C
European/International
Technical
less than or equal to Z
.
sys
max
▪ EN/IEC 61000‑3‑12 provided that the short-circuit power S
greater than or equal to the minimum S
point between the user's supply and the public system.
▪ EN/IEC
61000‑3‑12
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16 A and ≤75 A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power S
minimum S
value.
sc
Model
LRYEN10A7Y1
LRNUN5A7Y1
is
sys

14 Electrical installation

value at the interface
sc
=
European/International
Technical
greater than or equal to the
sc
Z
Minimum S
max
value
4337
2294
Installation and operation manual
is
sc
sc
25