High Voltage Wiring - Outdoor Unit - Daikin LRYEN-AY1 Installation And Operation Manual

Co₂ conveni-pack outdoor unit and capacity up unit
Table of Contents

Advertisement

Low noise switch
OFF
ON
Wiring low noise switch:
Wiring
Maximum wiring length
14.6.2
High voltage wiring – Outdoor unit
Connections/routing/fixing
X4M
1
X1M
PE
2
a d/e/f/g
X1M
Power supply:
a: Power supply cable
b: Overcurrent fuse
c: Earth leakage circuit breaker
PE
Protective earth (screw)
X4M
Output signals:
d: Caution
e: Warning
f: Run
g: Operation
1
X4M
X1M
h
Wiring intake (knockout hole) for high voltage. See
"14.3 Guidelines when knocking out knockout
holes" [ 4  27].
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit and capacity up unit
4P605461-1B – 2020.08
Mode
Normal mode
Low noise mode
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
130 m
X1M
PE
L1 L2 L3
N
a
b
c
L1 L2 L3 N
3N~ 50 Hz
380-415 V
X4M
C C1 W1 R P1 P2
d
e
f
g
2
h
PE
14 Electrical installation
Details – Output signals
NOTICE
Output signals. The outdoor unit is provided with a
terminal (X4M) that can output 4 different signals. The
signal is 220~240 V AC. The maximum load for all signals
is 0.5  A. The unit outputs a signal in the following
situations:
▪ C/C1: caution signal – connection recommended –
when an error occurs that does not stop unit operation.
▪ C/W1: warning signal – connection recommended –
when an error occurs that causes unit operation to
stop.
▪ R/P2: run signal – connection optional – when the
compressor is running.
▪ P1/P2: operation signal – connection mandatory –
when
the
expansion
showcases and blower coils are being controlled.
NOTICE
The operation output P1/P2 of the outdoor unit must be
connected to all expansion valves of the connected
showcases and blower coils. This connection is required
because the outdoor unit must be able to control the
expansion valves during startup (to prevent liquid
refrigerant from entering the compressor) and to prevent
opening of safety valve at the low pressure side of the
refrigeration cabinet.
Check on site that the expansion valve of the showcase or
blower coil can ONLY open when P1/P2 signal is ON.
Wiring output signals:
Wiring
Maximum wiring length
Details – Power supply
See
"14.5 Specifications of standard wiring
14.7
Connections to the capacity up
unit
NOTICE
▪ Be sure to keep the power line and transmission line
apart from each other (≥50  mm). Transmission wiring
and power supply wiring may cross, but may not run
parallel.
▪ Transmission wiring and power supply wiring may not
touch internal piping in order to avoid wire damage due
to high temperature piping.
▪ Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.
Low voltage wiring
▪ DIII transmission wiring
▪ Remote switches (operation, low
noise)
High voltage wiring
▪ Output signals (caution, warning,
run)
▪ Power supply (including earth)
valves
of
the
connected
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
130 m
components" [ 4  27].
Installation and operation manual
29