14 Electrical installation
(a)
If the total transmission wiring exceeds these limits,
communication errors might occur.
Remote switches
See details in:
"14.6.1 Low voltage wiring – Outdoor
"14.7.1 Low voltage wiring – Capacity up
Output signals
See details in:
"14.6.2 High voltage wiring – Outdoor
"14.7.2 High voltage wiring – Capacity up
14.6

Connections to the outdoor unit

NOTICE
▪ Be sure to keep the power line and transmission line
apart from each other (≥50  mm). Transmission wiring
and power supply wiring may cross, but may not run
parallel.
▪ Transmission wiring and power supply wiring may not
touch internal piping in order to avoid wire damage due
to high temperature piping.
▪ Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.
Low voltage wiring
▪ DIII transmission wiring
▪ Remote switches (operation, low
noise)
High voltage wiring
▪ Output signals (caution, warning,
run, operation)
▪ Power supply (including earth)
14.6.1
Low voltage wiring – Outdoor unit
Connections/routing/fixing
X1M (A1P)
1
X5M
2
d/e
a/b/c
X1M (A1P)
DIII transmission wiring:
a: To capacity up unit
b: To indoor units (air conditioning)
c: To communication box
X5M
Remote switches:
d: Remote operation switch
e: Remote low noise switch
Installation and operation manual
28
unit" [ 4  28]
unit" [ 4  30]
unit" [ 4  29]
unit" [ 4  30]
X1M (A1P)
TO
TO
TO
IN/D UNIT
OUT/D UNIT
MULTI UNIT
F1
F2
F1
F2 Q1 Q2
a
b
c
X5M
1
2
3
d
e
1
X1M (A1P)
X5M
f
Wiring intake (knockout hole) for low voltage. See
"14.3 Guidelines when knocking out knockout
holes" [ 4  27].
Details – DIII transmission wiring
See
"14.5 Specifications of standard wiring
Details – Remote operation switch
NOTICE
Remote operation switch. The unit is factory-equipped
with an operation switch with which you can turn unit
operation ON/OFF. If you want to remotely turn ON/OFF
operation of the outdoor unit, a remote operation switch is
required. Use a voltage-free contact for microcurrent
(≤1  mA, 12  V  DC). Connect to X5M/1+2, and set to
"Remote".
S1S
Factory-equipped operation switch:
OFF: Unit operation turned OFF
ON: Unit operation turned ON
Remote: Unit controlled (ON/OFF) with remote operation
switch
Wiring remote operation switch:
Wiring
Maximum wiring length
Details – Remote low noise switch
NOTICE
Low noise switch. If you want to remotely turn ON/OFF
low noise operation, you must install a low noise switch.
Use a voltage-free contact for microcurrent (≤1  mA,
12 V DC).
CO₂ Conveni-Pack outdoor unit and capacity up unit
2
f
components" [ 4  27].
OFF
S1S
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
130 m
LRYEN10A7Y1+LRNUN5A7Y1
4P605461-1B – 2020.08