Installer Settings: Tables To Be Filled In By Installer; Quick Wizard; Space Heating/Cooling Control; Domestic Hot Water Control [A.4] - Daikin Altherma EDLQ011-016C3W1 Operation Manual

Low temperature monobloc
Table of Contents

Advertisement

4 Energy saving tips

3.8
Installer settings: Tables to be
filled in by installer
3.8.1

Quick wizard

Setting
Space heating/cooling settings [A.2.1]
Unit control method
User interface location
Number of LWT zones
Pump operation mode
Glycol present
Outdoor unit [A.2.2]
DHW pump
External sensor (outdoor)
Control box [A.2.2.E]
Backup heater steps
BUH type
Preferential kWh rate
DHW operation
Contact type main
Contact type add.
Option box [A.2.2.F]
Ext. backup heat src
Alarm output
External kWh meter 1
External kWh meter 2
External sensor (indoor)
Capacities [A.2.3]
Booster heater
BUH: step 1
BUH: step 2
3.8.2

Space heating/cooling control

Setting
Leaving water temperature: Main zone [A.3.1.1]
LWT setpoint mode
Leaving water temperature: Additional zone [A.3.1.2]
LWT setpoint mode
Leaving water temperature: Delta T source [A.3.1.3]
Heating
Cooling
Leaving water temperature: Modulation [A.3.1.1.5]
Modulated LWT
Leaving water temperature: Emitter type [A.3.1.1.7]
Emitter type
3.8.3

Domestic hot water control [A.4]

Setting
Type
Operation manual
8
Default
Fill in...
2 (RT)
1 (Room)
0 (1 LWT zone)
2 (Request)
0 (No)
0 (No)
0 (No)
EBLQ/
EDLQ*CAV3+W1:
0 (No BUH)
EBLQ/EDLQ*CA3*:
1 (1 step)
1 (1P,(1/1+2))
0 (No)
0 (No)
1 (Thermo)
1 (Thermo)
0 (No)
0 (NO)
0 (No)
0 (No)
0 (No)
3 kW
3 kW
0 kW
Default
Fill in...
1 (WD)
1 (WD)
5°C
5°C
1 (Yes)
0 (Quick)
Default
Fill in...
1 (R+S)
Setting
Maximum setpoint
INFORMATION
There is a risk of space heating (cooling) capacity
shortage/comfort problem (in case of frequent domestic hot
water operation, frequent and long space heating/cooling
interruption will happen) when selecting [6‑0D]=0 ([A.4.1]
Domestic hot water Type=Reheat only) in case of a
domestic hot water tank without an internal booster heater.
INFORMATION
When the DHW tank booster mode is active, the risk of
space heating/cooling and capacity shortage comfort
problems is significant. In case of frequent domestic hot
water operation, frequent and long space heating/cooling
interruptions will happen.
3.8.4

Contact/helpdesk number [6.3.2]

Setting
Contact/helpdesk number
4
Energy saving tips
Tips about room temperature
▪ Make sure the desired room temperature is NEVER too high (in
heating mode) or too low (in cooling mode), but ALWAYS
according to your actual needs. Each saved degree can save up
to 6% of heating/cooling costs.
▪ Do NOT increase the desired room temperature to speed up
space heating. The space will NOT heat up faster.
▪ When your system layout contains slow heat emitters (example:
under floor heating), avoid large fluctuation of the desired room
temperature and do NOT let the room temperature drop too low. It
will take more time and energy to heat up the room again.
▪ Use a weekly schedule for your normal space heating or cooling
needs. If necessary, you can easily deviate from the schedule:
▪ For shorter periods: You can overrule the scheduled room
temperature. Example: When you have a party, or when you
are leaving for a couple of hours.
▪ For longer periods: You can use the holiday mode. Example:
When you stay at home during your holiday, or when you go
away during your holiday.
Tips about DHW tank temperature
▪ Use a weekly schedule for your normal domestic hot water needs
(only in scheduled mode).
▪ Program to heat up the DHW  tank to a preset value (Storage
comfort = higher DHW  tank temperature) during the night,
because then space heating demand is lower.
▪ If heating up the DHW  tank once at night is not sufficient,
program to additionally heat up the DHW tank to a preset value
(Storage eco = lower DHW tank temperature) during the day.
▪ Make sure the desired DHW  tank temperature is NOT too high.
Example: After installation, lower the DHW tank temperature daily
by 1°C and check if you still have enough hot water.
▪ Program to turn ON the domestic hot water pump only during
periods of the day when instant hot water is necessary. Example:
In the morning and evening.
Daikin Altherma low temperature monobloc
Default
Fill in...
60°C if E-07=0
80°C if E-07=5
Default
Fill in...
EBLQ+EDLQ011~016CA(3)V3+W1
4P537989-1 – 2018.05

Advertisement

Table of Contents
loading

Table of Contents