VENTING

The venting system must be installed properly following all local codes
or in the absence of local codes, the latest edition of the National Fuel
Gas Code (ANSI Z223.1- latest edition), or in Canada, The Natural Gas
and Propane Installation Code (B149.1-00 latest edition). Failure to
properly install the venting system could result in property damage,
personal injury, or death.
Carefully inspect the venting system of a replacement water heater
installation before connecting to the venting system. All joints in the
vent connector must be securely fastened with screws and fit tightly
together. Inspect the venting system for signs of deterioration (rust and
perforation) and replace any sections that are not in good condition.
The chimney must be lined and in good condition. Check to make sure
the venting system is properly sized for the water heater. If the venting
system was previously sized for another gas appliance that has been
removed, the venting system may now be too large. Refer to the latest
edition of the National Fuel Gas Code (ANSI Z223.1-latest edition), or in
Canada, the Natural Gas and Propane Installation Code (B149.1-00
latest edition) for the correct sizing of venting systems and common
venting with another gas appliance.
Do not vent this water heater into the venting system of another gas
appliance designed to vent under positive pressure.
The water heater should be installed as close as practical to the venting
system to minimize the vent connector length required. Refer to local
codes for the distance limitations on vent connector lengths.
At the completion of the water heater installation, the burner and venting
system must be checked for proper operation with all other commonly
vented appliances in operation. Check for spillage of flue products
around the outside relief opening of the draft hood after several minutes
of operation. The flame from a match should be drawn into the draft
hood. Do not use the water heater or connected equipment if spillage is
detected until the problem is corrected. Refer to the latest edition of the
National Fuel Gas Code, or in Canada, the Natural Gas and Propane
Installation Code for complete details on the "Procedure to Be Followed
to Place Equipment in Operation".
This water heater has been shipped with a draft diverter for which it was
designed with reference to the horizontal and vertical planes. If removed, the
draft diverter must be replaced in the same position and secured to the jacket
top by the screws with which it was installed.
WARNING
WARNING