Samsung AM280FNHDEH Installation Manual page 28

Hide thumbs Also See for AM280FNHDEH:
Table of Contents

Advertisement

Setting an indoor unit address and installation option (Continued)
Setting an indoor unit installation option (suitable for the condition of each installation location)
1.
Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power
supply in the indoor unit.
2.
The panel(display) should be connected to an indoor unit to receive option.
3.
Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is
"020010-100000- 200000-300000".
- Individual control of a remote controller(SEG20) is the function that controls an
indoor unit individually when there is more than one indoor unit.
4.
Set the indoor unit option by wireless remote controller.
 02 series installation option
SEG1
0
SEG7
1
SEG13
2
SEG19
Individual control of a
3
 1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain pump is set to 0.
 1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using filter(SEG18) will be set to '1000hour' even if the SEG18 is set to
 When setting the option other than above SEG values, the option will be set as "0".
 SEG5 central control option is basically set as 1 (Use), so you don't need to set the central control option additionally.
However, if the central control is not connected but it doesn't indicate an error message, you need to set the central control
option as 0 (Disuse) to exclude the indoor unit from the central control.
 The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
F1
F2
COM1
OUTDOOR
DC 12 V
COMMUNICATION
 The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
28
SEG2
SEG3
2
-
SEG8
SEG9
Drain pump
Hot water heater
SEG14
SEG15
External control output /
External control
External heater On or Off
signal
SEG20
SEG21
Heating setting
compensation / Removing
remote controller
condensated water in
heating mode
exept for 2 or 6.
V1
V2
F3
F4
1(L) 2(N)
1
(+)
(-)
COM2
L
N
Wire Remote
AC
HOT
Controller
POWER
COIL
SEG4
External room
temperature sensor /
Minimizing fan operation
when thermostat is off
SEG10
-
SEG16
S-Plasma ion
SEG22
EEV Step of stopped unit
during oil return/defrost
mode
* The output of hot coil terminal is AC 220 V / 230 V
(The same as Indoor Unit's input Power)
2
Indoor Unit
1(L)
F2
2(N)
F1
SEG5
SEG6
FAN RPM
Central control
compensation
SEG11
SEG12
EEV Step when
-
heating stops
SEG17
SEG18
Number of hours
Buzzer
using filter
SEG23
SEG24
Motion detect sensor
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Am fnhdeh series

Table of Contents