Figure 11 Motor Connections - Bard J18AA-A Installation Instructions Manual

Wall mounted packaged air conditioner
Table of Contents

Advertisement

TROUBLESHOOTING GE X13-SERIES ECM2.3
2. If the motor has proper high voltage and ground at
the (L/L1) (G) (N/L2) connections, then continue
Model X13 Communication Diagnostics
with the "Model SelecTech Communication
The X13 motor is communicated through 24 VAC low voltage
Diagnostics".
(Thermostat Control Circuit Wiring).
Model SelecTech Communication Diagnostics
1.
Start with unit wiring diagram to confirm proper
connections and voltage (see Figure 11).
The SelecTech motor is communicated through 24 VAC
low voltage (Thermostat Control Circuit Wiring).
1. Start with unit wiring diagram to confirm proper
connections and voltage (see Figure 11).
2. Initiate a demand from the thermostat and
check the voltage between the common and the
appropriate motor terminal (1-5). ("G" input is
typically on terminal #1, but always refer to wiring
diagram.)
24VAC Common
24VAC "R" Signal through
thermostat output.
24VAC Common
24VAC "R" Signal through
thermostat output.
A. If the low voltage communication is not
present, check the demand from the
2. Initiate a demand from the thermostat and check the
thermostat. Also check the output terminal
voltage between the common and the appropriate motor
and wire(s) from the terminal strip or control
terminal (1-5). ("G" input is typically on terminal #1, but
relay(s) to the motor.
refer to wiring diagram!)
a. If the low voltage communication is not present, check
B. If the motor has proper high voltage as
the demand from the thermostat. Also check the
identified above (Motor not Running #1),
output terminal and wire(s) from the terminal strip or
proper low voltage to a programmed terminal
control relay(s) to the motor.
and is not operating, the motor is failed and
b. If the motor has proper high voltage as identified
will require replacement.
above (Motor not Running #1), and proper low voltage
to a programmed terminal, and is not operating, the
motor is failed, and will require replacement.
FIGURE 11
FIGURE 11
Motor Connections
MOTORS
CONT'D.
Manual
2100-467H
Page
23 of 23
Manual 2100-651D
Page
23 of 32