11-2-3.Only outdoor unit does not run.

A. Check setting temperature.
COOL
Is room temperature too low ?
Try to lower setting temperature by
temperature setting button cooler.
• Try to run using another remote
control unit.
Remote control unit is defective.
B. Check PCB Ass'y in either indoor or outdoor unit.
• Check voltage between terminals
No. 3(+) and No. 4 at terminal plate.
(DC 24V)
• Indoor PCB Ass'y is defective.

11-2-4.Only indoor unit does not run.

• Indoor PCB Ass'y is defective.
NO
Outdoor unit still does
not run.
OK
OK
No voltage appears.
HEAT
Is room temperature too high ?
Try to raise setting temperature by
temperature setting button warmer.
• Try to run using another remote
control unit.
Remote control unit is defective.
• Outdoor PCB Ass'y is defective.
32
NO
Outdoor unit still does
not run.
OK