1
Fig. 30 Gas valve
[1]
ON/OFF knob (shown in ON position)
15.5

Cleaning the boiler

The boiler can be cleaned with brushes and/or by wet cleaning. Cleaning
tools are available as accessories.
Inspecting the ignition burner
▶ Observe the ignition burner through the sight glas window
( figure 31).
Fig. 31 GC 144 II
[1]
Sight glass
▶ The flame must rise over the sensor by ½" to 1-½".
▶ The pilot ignition gas pressure must be adjusted if the flame is too
small or too large.
The adjustment screw is located behind a safety screw
on the gas valve ( figure 33).
Logano GC 144 II – 6 720 808 893 (2017/02)
6 720 804 440-38.1T
1
6 720 804 440-39.1T
Boiler inspection and maintenance
1
Fig. 32 Correct ignition flame setting
[1]
Flame rises ½" to 1-½" above sensor
[2]
Ignition flame
▶ Remove the safety screw on the adjustment screw for the igniter
( figure 24, page 17).Turn the inner adjustment screw clockwise
to reduce the size of the ignition flame, and counterclockwise to
increase it.
▶ After completed adjustment replace the safety screw
( figure 24, page 17).
▶ If the flame is too small, the pilot orifice needs cleaning
( figure 39, page 23). If the igniter flame is acceptable, start
cleaning.
Be careful not to damage the pilot orifice during
installation and cleaning.
1
Fig. 33 Gas valve
[1]
Safety screw on igniter adjustment screw
15
2
6 720 804 440-40.1T
6 720 804 440-41.1T
21