SERVICE HINTS

1. Caution user to maintain clean air filters at all
times and to not needlessly close off supply air
registers. This may reduce airflow through the
system, which shortens equipment service life as
well as increasing operating costs and noise levels.
2. Switching to heating cycle at 75°F or higher
outside temperature may cause a nuisance trip
of the remote reset high pressure switch. Turn
thermostat off, then on, to reset the high pressure
switch.
3. Heat pump wall thermostats perform multiple
functions. Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.
4. Check all power fuses or circuit breakers to be sure
they are the correct rating.
5. Periodic cleaning of the outdoor coil to permit full
and unrestricted airflow circulation is essential.
6. Some service requires the need to remove the
unit from the wall including replacement of the
indoor coil and/or the outdoor coil. Also, servicing
the outdoor fan motor or fan blade will require
removing the unit from the wall if the unit is
installed at a height that is not easily accessible
from the outside of the building.
In order to remove the unit from the wall, the
following procedure must be used:
a.
Turn off power to the unit at the remote
location. Some units may have more than one
power supply.
b. Disconnect field wiring at unit terminal block
and remove from unit.
c.
Disconnect condensate drain.
d. Remove the lower skirting around the unit.
e.
Remove wall mounting brackets from wall
on each side of the unit and/or remove the
internal bolts in the lower section securing
unit to wall sleeve.
f.
If unit is attached to duct work, remove upper
cabinet extension by removing the top center
screw only from the cabinet side panel.
g.
Remove screws that attach the duct work to
the unit flanges.
This unit is equipped with four rollers mounted
to the base. For ease in pulling unit out from
the wall, it may be desirable to remove the
bottom service door, which requires removal of
the return air panel. Grip the front flange of
the base pan and pull straight out.
7. Annual maintenance is required to make sure that
all of the systems are functioning properly.
a.
Check to make sure that the drains are not
obstructed in any way.
b. Remove any debris in the condenser section of
the unit.
c.
Inspect and clean mist eliminator as described
below.
d. Inspect and wash outdoor coil as necessary.

MIST ELIMINATOR SERVICE

A mist eliminator is supplied with the wall sleeve. The
mist eliminator is constructed of an aluminum frame
and mesh. The mist eliminator is located in the top
section of the wall sleeve and can be removed from the
inside of the building without removing the unit from
the wall. This requires that the ventilation package be
removed.
It is recommended that the mist eliminator be
inspected annually and serviced as required. The mist
eliminator can be inspected from the outside of the
building by looking through the outdoor grille. The
mist eliminator can be serviced from the outside by
using a vacuum cleaner. The outdoor grille must be
removed. Use the vacuum to remove dirt and debris
from the surface of the mist eliminator. If additional
cleaning is required, the mist eliminator will have to be
removed from the sleeve.
The ventilation package will have to be removed to gain
access to the mist eliminator. If the blank-off plate
option is used, it is not necessary to service the mist
eliminator. The steps necessary to remove each of the
vent options are listed on the following pages.
The mist eliminator can be cleaned by washing with
soap and water. The excess water should be shaken off
the mist eliminator before it is reinstalled.