Phase Monitor; Condenser Fan Operation; Service Hints; Sequence Of Operation - Bard W42HC-A Installation Instructions Manual

Wall mount heat pump
Hide thumbs Also See for W42HC-A:
Table of Contents

Advertisement

However, three phase compressors will rotate in either
direction depending upon phasing of the power.
Since there is a 50-50 chance of connecting power
in such a way as to cause rotation in the reverse
direction, verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as substantially
reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the time
the equipment is put into service. If improper rotation
is corrected at this time, there will be no negative
impact on the durability of the compressor. However,
reverse operation for over 1 hour may have a negative
impact on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for an extended period of time, the
compressor's internal protector will trip.
All three phase compressors are wired identically
internally. As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.
The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

Phase Monitor

All units with three phase scroll compressors are
equipped with a three phase line monitor to prevent
compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two
LEDs. If the Y signal (call for cooling) is present at the
phase monitor and phases are correct, the green LED
will light.
NOTE: The phase monitor will not show phase reversal
until the compressor is energized during a call for
cooling or heat pump operation.
If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply
leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.

Condenser Fan Operation

NOTE: Certain models may be equipped with a low
ambient control (LAC), and if so, the condenser fan
motor will have a delayed start until system refrigerant
operating pressure builds up. After starting, the fan
motor may or may not cycle depending upon ambient
conditions. This is normal operation.
Manual 2100-711F
Page
24 of 45

Service Hints

1. Caution owner/operator to maintain clean air filters
at all times and also not to needlessly close off
supply and return air registers. This reduces airflow
through the system, which shortens equipment
service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure
they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full
and unrestricted airflow circulation is essential

Sequence of Operation

Cooling

Circuit R-Y1 makes at thermostat pulling in compressor
contactor, starting the compressor and outdoor motor.
(See NOTE under Condenser Fan Operation
concerning models equipped with low ambient
control.) The G (indoor motor) circuit is automatically
completed by the thermostat on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation. On a call for 2nd
stage heating, circuit R-W2 makes at the thermostat
pulling in heat contactor for the strip heat and blower
operation. On a call for third stage heat, R-W3 makes
bringing on second heat contactor, if so equipped.

Heating

A 24V solenoid coil on reversing valve controls heating
cycle operation. Two thermostat options, one allowing
"Auto" changeover from cycle to cycle and the other
constantly energizing solenoid coil during heating
season—thus eliminating pressure equalization noise
except during defrost, are to be used.
On "Auto" option, a circuit is completed from R-B/W1
and R-Y1 on each heating "on" cycle, energizing reversing
valve solenoid and pulling in compressor contactor,
starting compressor and outdoor motor. R-G also make
starting indoor blower motor. Heat pump heating cycle
now in operation.
The second option has no "Auto" changeover position, but
instead energizes the reversing valve solenoid constantly
whenever the system switch on subbase is placed in
"Heat" position, the "B" terminal being constantly
energized from R. A thermostat demand for heat
completes R-Y1 circuit, pulling in compressor contactor
starting compressor and outdoor motor. R-G also make
starting indoor blower motor.
On a call for 2nd stage heating, circuit R-W2 makes
at the thermostat pulling in the heat contactor for the
strip heat and blower operation. On a call for third
stage heat, R-B/W1 breaks, dropping out heat pump,
and R-W3 makes, bringing on second heat contactor, if
so equipped.
.

Advertisement

Table of Contents
loading

Table of Contents