Master Programming Level
ANN-80 Options Screen
Pressing 2 while viewing ANN-BUS screen #2 will display the following screen:
The Piezo Enable option allows the programmer to select whether the piezo sounder on any installed ANN-80 module will ever sound.
Pressing 1 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not the ANN-80 annunciator must be unlocked by its key before any
annunciator key presses will function. Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select whether the Ack/Step button on any
installed ANN-80 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1
causes the display to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No (Ack/Step button
never functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the Silence button on any installed
ANN-80 annunciator will function normally or always be ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes the
display to toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the Reset button on any installed ANN-
80 annunciator will function normally or always be ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display
to toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never functions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the Drill button on any installed ANN-80
annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to
toggle between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never functions).
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
Zone 5 Alarm
Zone 6 Alarm
Zone 7 Alarm
Zone 8 Alarm
Zone 9 Alarm
Zone 10 Alarm
Zone 1 Trouble
Zone 2 Trouble
Zone 3 Trouble
Zone 4 Trouble
Zone 5 Trouble
Zone 6 Trouble
Zone 7 Trouble
Zone 8 Trouble
Zone 9 Trouble
Zone 10 Trouble
Zone 1 Supervisory
Zone 2 Supervisory
Zone 3 Supervisory
Zone 4 Supervisory
Zone 5 Supervisory
Zone 6 Supervisory
Zone 7 Supervisory
Zone 8 Supervisory
Zone 9 Supervisory
Zone 10 Supervisory
ANN-80 OPTIONS
1=SIL BTN ENABLE
2=RST BTN ENABLE
3=DRL BTN ENABLE
ANN-80 Options Screen #2
Programming
73

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents