Input Circuits
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to "CAC-5X
Class A Converter Module" on page 31.
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
UL listed Power Supervision Relay
UL listed compatible 4-wire smoke detector
manual pull stations
heat detectors
Figure 2.5 IDC Connections
Installation
UL listed compatible
2-wire smoke detectors
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
25