Operating Power

Left Side
2.2 Operating Power
WARNING: RISK OF ELECTRICAL SHOCK AND/OR EQUIPMENT DAMAGE
!
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES
OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING
AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Refer to AC Power in the section titled "Specifications" on page 13,
for power and current requirements for each FACP version. Run a pair of wires (with ground conductor) from the protected premises
main breaker box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code, use 14 AWG (2.00 mm
1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other equipment may be connected to this circuit. In addition, this circuit
must be provided with overcurrent protection and may not contain any power disconnect devices. An Earth Ground connection must be
made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00
mm
)] to the grounding stud in the backbox and then run the wire to TB1. Do not use conduit for the Earth Ground connection since this
2
does not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit board using the plug-in connector and
cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the
system is in alarm.
WARNING: SULFURIC ACID
!
BATTERIES CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN
DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH
WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
Top
Door = 19.26" (48.92 cm)
Backbox = 19.0" (48.26)
Bottom
Figure 2.3 Backbox and Battery Box
Door = 16.821" (42.73 cm)
Backbox = 16.65" (42.29 cm)
Installation
Depth = 5.207" (13.23 cm)
Depth = 5.257"
(13.353 cm)